Brake Answer Waiting Time
Program
Protection
Special Protection Parameters
This parameter is used in conjunction with the discrete input terminal setting
64
[
System Consistent Sequence
(BA: braking answer)] (see item 64 of
for additional information on this feature).
After activating the discrete input terminal
System Consistent Sequence
(B:
braking release), the setting of this parameter defines a window of time in
which 1) a
Braking Answer
response must be received, or 2) the brake must
release.
Should this timer setting expire before the
Braking Answer
is returned or the
brake releases, a
Brake Fault
(E-11)
is incurred. Otherwise, the brake releases
and normal motor operations resume.
Direct Access Number — F630
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 10.00
Units — Seconds
Brake Release After Run Timer
Program
Protection
Special Protection Parameters
This parameter sets the time that the brake will hold after the
Run
command
criteria has been met.
Direct Access Number — F632
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Earth Fault Alarm Level
Program
Special
Earth Fault
This parameter sets the threshold level (%) that must be exceeded to meet the
Earth Fault Alarm
activation criteria.
Direct Access Number — F640
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
No
Minimum — 0
Maximum — 100
Units — %
Earth Fault Alarm Time
Program
Special
Earth Fault
In the event that the
Earth Fault Alarm
activation criteria is met, a timer
begins to count down to zero. Upon reaching zero, the
Earth Fault Alarm
is
activated.
This parameter sets the start-time of the count-down timer.
Direct Access Number — F641
Parameter Type —
Numerical
Factory Default —
1.00
Changeable During Run —
No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Earth Fault Trip Level
Program
Special
Earth Fault
This parameter sets the threshold level (%) that must be exceeded to meet the
Earth Fault Trip
activation criteria.
Direct Access Number — F642
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
No
Minimum — 0.00
Maximum — 100
Units — %