WX9 ASD Installation and Operation Manual
97
V/f Five-Point 3 Frequency
Program
Special
V/f Five-Point Setting
The
V/f Five-Point 3 Frequency
sets the frequency to be associated with the
V/f Five-Point 3 Voltage
(
).
See
V/f Five-Point 1 Frequency
(
) for additional information on custom
V/f curves.
Direct Access Number — F194
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 299
Units — Hz
V/f Five-Point 3 Voltage
Program
Special
V/f Five-Point Setting
The
V/f Five-Point 3 Voltage
establishes the percentage of the output voltage
that is to be associated with the frequency setting of
the
V/f Five-Point 3
Frequency
.
The
Current/Voltage Units Setup
) setting will determine if the
selection for this parameter appears in the form of a Voltage (V) or as a
Percentage (%) of the ASD rating.
The default setting is %.
See
V/f Five-Point 1 Frequency
(
F190)
for additional information on custom
V/f curves.
Direct Access Number — F195
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 100.0
Units — %
V/f Five-Point 4 Frequency
Program
Special
V/f Five-Point Setting
The
V/f Five-Point 4 Frequency
sets the frequency to be associated with the
V/f Five-Point 4 Voltage
(
).
See
V/f Five-Point 1 Frequency
(
F190)
for additional information on custom
V/f curves.
Direct Access Number — F196
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 299
Units — Hz
V/f Five-Point 4 Voltage
Program
Special
V/f Five-Point Setting
The
V/f Five-Point 4 Voltage
establishes the percentage of the output voltage
that is to be associated with the frequency setting of
V/f Five-Point 4
Frequency
The
Current/Voltage Units Setup
) setting will determine if the
selection for this parameter appears in the form of a Voltage (V) or as a
Percentage (%) of the ASD rating.
The default setting is %.
See
V/f Five-Point 1 Frequency
(
) for additional information on custom
V/f curves.
Direct Access Number — F197
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 100.0
Units — %
V/f Five-Point 5 Frequency
Program
Special
V/f Five-Point Setting
The
V/f Five-Point 5 Frequency
sets the frequency to be associated with the
V/f Five-Point 5 Voltage
(
).
See
V/f Five-Point 1 Frequency
(
F190)
for additional information on custom
V/f curves.
Direct Access Number — F198
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 299
Units — Hz