WX9 ASD Installation and Operation Manual
145
Regenerative Braking Torque Limit 2 Level
(250% = disabled)
Program
Torque
Manual Torque Limit Settings
This parameter is used to set the negative torque upper-limit for the
2 Motor
Profile
when multiple motors are controlled by a single drive or when a single
motor is controlled by multiple profiles.
Direct Access Number — F445
Parameter Type —
Numerical
Factory Default —
250.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Power Running Torque Limit 3 Level (250% = disabled)
Program
Torque
Manual Torque Limit Settings
This parameter is used to set the positive torque upper-limit for the
3 Motor
Profile
when multiple motors are controlled by a single drive or when a single
motor is controlled by multiple profiles.
Direct Access Number — F446
Parameter Type —
Numerical
Factory Default —
250.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Regenerative Braking Torque Limit 3 Level
(250% = disabled)
Program
Torque
Manual Torque Limit Settings
This parameter is used to set the negative torque upper-limit for the
3 Motor
Profile
when multiple motors are controlled by a single drive or when a single
motor is controlled by multiple profiles.
Direct Access Number — F447
Parameter Type —
Numerical
Factory Default —
250.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Power Running Torque Limit 4 Level (250% = disabled)
Program
Torque
Manual Torque Limit Settings
This parameter is used to set the positive torque upper-limit for the
4 Motor
Profile
when multiple motors are controlled by a single drive or when a single
motor is controlled by multiple profiles.
Direct Access Number — F448
Parameter Type —
Numerical
Factory Default —
250.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Regenerative Braking Torque Limit 4 Level
(250% = disabled)
Program
Torque
Manual Torque Limit Settings
This parameter is used to set the negative torque upper-limit for the
4 Motor
Profile
when multiple motors are controlled by a single drive or when a single
motor is controlled by multiple profiles.
Direct Access Number — F449
Parameter Type —
Numerical
Factory Default —
250.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Torque Limit Mode
Program
Torque
Torque Limit Settings
Contact the TIC Customer Support Center for information on this parameter.
Settings:
0 — Power Running/Regenerative Torque Limit
1 — Positive/Negative Torque Limits
Direct Access Number — F450
Parameter Type —
Selection List
Factory Default —
Power Running /
Regenerative Torque
Limit
Changeable During Run —
No