42
No.
13
14
Item
Display of
[ OPERATION
READY]
[ PRE-HEAT]
Selection of
central control
mode
Outline of specifications
<OPERATION READY>
Displayed on the remote controller
1) When the following check codes are indicated
• Open phase of power supply wiring [P05] was detected.
• There is an indoor unit that detected the indoor
overflow [P10].
• There is an indoor unit that detected the interlock alarm
[L30].
2) During Force Thermo-OFF
• [COOL/DRY] operation is unavailable because the
other indoor unit operates with [HEAT] mode.
• [HEAT] operation is unavailable because COOL priority
(SW11-bit1 of the Outdoor I/F P. C. board is ON) is set and
the other indoor unit operates with [COOL/DRY] mode.
3) The above indoor units that cannot operate stay in
Thermo-OFF status.
4) The indoor fan stops because the system performs
[Recovery operation for heating refrigerant (Oil)].
<PRE-HEAT>
Displayed on the remote controller
The indoor fan stops in order to prevent discharge of cool air
when heating operation started or during heating operation.
(including the defrost operation during thermo-OFF)
1) Selection of the contents that can be operated by the remote controller at the
indoor unit side is possible according to setting at the central controller side.
2) Setting contents
• In case of TCC-LINK central control
(
{
: Operation possible
×
: Operation impossible)
• In case of wired remote controller type, [Central control
] display (Goes on) in the
central control mode
• Display flashes when an item of the operation prohibited was changed on the remote
controller.
• In case of wireless remote controller type, the display lamp does not change but the
contents that can be operated are same in the central control mode.
(
∗
1) The operation from the wireless remote controller in the central control mode is
notified with the receiving sound, Pi, Pi, Pi, Pi, Pi (5 times).
(
∗
1)
If the operation select modes are different in the central 2 to 4 from those at the
central controller side, the operations Temp. Setting, air volume setting, and air
direction setting are inoperable.
Remarks
•
<
>
display
No display for wireless
remote controller
•
< >
display
Operation from
TCC-LINK
central control
Individual
[Central 1]
[Central 2]
[Central 3]
[Central 4]
Operation on RBC-AMT32UL
ON/OFF
Operation
Timer
Temp.
Air speed
Air direction
setting
selection
setting
setting
setting
setting
{
{
{
{
{
{
×
{
×
{
{
{
×
×
×
×
{
{
{
×
{
×
{
{
{
×
{
{
{
{
On
RBC-AMT32UL
No display
[Central control
]
display
Summary of Contents for Carrier MMC-AP0181H2UL
Page 12: ...12 MMU AP0152H2UL AP0182H2UL ...
Page 13: ...13 MMU AP0212H2UL MMU AP0242H2UL MMU AP0302H2UL ...
Page 14: ...14 MMU AP0362H2UL MMU AP0422H2UL ...
Page 15: ...15 2 2 Compact 4 Way Cassette Type MMU AP0071MH2UL MMU AP0091MH2UL MMU AP0121MH2UL ...
Page 16: ...16 MMU AP0151MH2UL MMU AP0181MH2UL ...
Page 156: ...156 MMU AP0152H2UL AP0182H2UL AP0212H2UL AP0242H2UL AP0302H2UL ...
Page 159: ...159 MMU AP0362H2UL AP0422H2UL ...
Page 168: ...168 11 3 Ceiling Type MMC AP0181H2UL AP0241H2UL AP0361H2UL AP0421H2UL ...
Page 174: ...174 MMK AP0153H AP0183H AP0243H ...