58
Procedure
1
2
3
4
5
Operation contents
Push [TEST] button for 4 seconds or more.
[TEST] is displayed at the display part and
the mode enters in TEST mode.
Push [ON/OFF] button.
Change the mode from [COOL] to [HEAT] using [MODE] button.
• Do not use [MODE] button for other mode except
[COOL]/[HEAT] modes.
• The temperature cannot be adjusted during test run.
• The error detection is performed as usual.
After test run, push [ON/OFF] button to stop the operation.
(Display on the display part is same to that in Procedure
1
.)
Push [TEST] button to clear the TEST mode.
([TEST] display in the display part disappears and
status becomes the normal stop status.)
7-3. Functions at test run
Cooling/Heating test run check
The test run for cooling/heating can be performed from either indoor remote controller or outdoor interface
P.C. board.
1. Start/Finish operation of test run
~
~
~
~
~
Test run from indoor remote controller
Wired remote controller: Refer to the below item of “Test run” of the wired remote controller.
Wireless remote controller: Refer to the next page item of “Test run” of the wireless remote controller.
In case of wired remote controller
Note)
The test run returns to the normal operation after 60 minutes.
<RBC-AMT32UL>
TEMP.
ON / OFF
SET
TIME
TIMER SET
TEST
FILTER
RESET
CL
FAN
SAVE
SWING/FIX
VENT
MODE
UNIT LOUVER
1,
5
2,
4
3
TEST
TEST
Summary of Contents for Carrier MMC-AP0181H2UL
Page 12: ...12 MMU AP0152H2UL AP0182H2UL ...
Page 13: ...13 MMU AP0212H2UL MMU AP0242H2UL MMU AP0302H2UL ...
Page 14: ...14 MMU AP0362H2UL MMU AP0422H2UL ...
Page 15: ...15 2 2 Compact 4 Way Cassette Type MMU AP0071MH2UL MMU AP0091MH2UL MMU AP0121MH2UL ...
Page 16: ...16 MMU AP0151MH2UL MMU AP0181MH2UL ...
Page 156: ...156 MMU AP0152H2UL AP0182H2UL AP0212H2UL AP0242H2UL AP0302H2UL ...
Page 159: ...159 MMU AP0362H2UL AP0422H2UL ...
Page 168: ...168 11 3 Ceiling Type MMC AP0181H2UL AP0241H2UL AP0361H2UL AP0421H2UL ...
Page 174: ...174 MMK AP0153H AP0183H AP0243H ...