32
No.
5
Item
Air speed
selection
(Continued)
Outline of specifications
<HEAT>
Remarks
Value in the parentheses indicates one when thermostat of
the remote controller works.
Value without parentheses indicates one when thermostat of
the body works.
• If the air speed has been changed once, it is not changed
for 1 minute. However when the air speed exchanged, the
air speed changes.
• When heating operation has started, select an upward
slope for the air speed, that is, the high position.
• If the temperature is just on the difference boundary, the
air speed does not change.
• In Tc2
≥
140°F[60°C], the air speed increases by 1 step.
Tc2: Indoor heat
exchanger sensor
temperature
6
Prevention of
cold air
discharge
1. In heating operation, the higher temperature of TC2 sensor
and TCJ sensor is compared with temperature of TC1
sensor and then the lower temperature is used to set the
upper limit of the fan tap.
• When B zone has continued for 6 minutes, the opera-
tion shifts to C zone.
• In defrost time, the control point is set to +10.8°F[6°C].
ITCJ: Temperature of
indoor heat
exchanger sensor
• In D and E zones,
priority is given to
remote controller air
speed setup.
• In A zone “ ” is dis-
played.
Ta ˚F [˚C]
(–0.9) Ð1.8 [(–0.5) –1.0]
(0) Tsh
(+0.9) +1.8 [(+0.5) +1.0]
(+1.8) +3.6 [(+1.0) +2.0]
(+2.7) +5.4 [(+1.5) +3.0]
(+3.6) +7.2 [(+2.0) +4.0]
L <L+>
L+ <H>
H <H+>
HH
<HH>
H+
<HH>
E
D
C
B
A
Body thermostat works.
Remote controller thermostat works.
< > : Indicate automatic heating.
E
B
A
A zone: OFF
B zone:
Over 72˚F [26˚C], below 82˚F [28˚C], ULTRA LOW (LL)
C zone:
Over 82˚F [28˚C], below 86˚F [30˚C], LOW (L)
D zone:
Over 86˚F [30˚C], below 90˚F [32˚C], MED (H)
E zone: HIGH (HH)
D
C
90 [32]
86 [30]
82 [28]
75 [26]
68 [20]
61 [16]
˚F [˚C]
Summary of Contents for Carrier MMC-AP0181H2UL
Page 12: ...12 MMU AP0152H2UL AP0182H2UL ...
Page 13: ...13 MMU AP0212H2UL MMU AP0242H2UL MMU AP0302H2UL ...
Page 14: ...14 MMU AP0362H2UL MMU AP0422H2UL ...
Page 15: ...15 2 2 Compact 4 Way Cassette Type MMU AP0071MH2UL MMU AP0091MH2UL MMU AP0121MH2UL ...
Page 16: ...16 MMU AP0151MH2UL MMU AP0181MH2UL ...
Page 156: ...156 MMU AP0152H2UL AP0182H2UL AP0212H2UL AP0242H2UL AP0302H2UL ...
Page 159: ...159 MMU AP0362H2UL AP0422H2UL ...
Page 168: ...168 11 3 Ceiling Type MMC AP0181H2UL AP0241H2UL AP0361H2UL AP0421H2UL ...
Page 174: ...174 MMK AP0153H AP0183H AP0243H ...