127
No.
3
Part name
Electric
parts box
Procedure
1. Detachment
1) Carry out works of Detachment of
1
and
2
.
2) Remove the power supply wire and the
remote control wire and control wires from
the terminal blocks.
3) Remove the power supply wire from cord
clamp at side of the electric parts box.
4) Remove screws (M4, 0.39"(10 mm), 2 pcs.))
of the electric parts box and pull out
downward.
5) Hook the hooking section temporarily at the
rear side of the electric parts box to the
sheet fittings part of the main unit.
2. Attachment
1) Insert the square hole of the electric parts
box into the claw of the main unit.
2) Attach screws (M4, 0.39"(10 mm), 2 pcs.))
to the electric parts box.
3) Connect the power supply wire and the
remote control wire and control wires as
before.
4) Carry out works of Attachment of
1
and
2
.
Remarks
Screw
Cord clamp
U
1
U
2
A B
L
1
L
2
Cord clamp
Control wiring/Remote
control terminal block
Power supply
terminal block
Claws of main unit
Square hole of
electric parts box
Sheeted folding up
section of main unit
Summary of Contents for Carrier MMC-AP0181H2UL
Page 12: ...12 MMU AP0152H2UL AP0182H2UL ...
Page 13: ...13 MMU AP0212H2UL MMU AP0242H2UL MMU AP0302H2UL ...
Page 14: ...14 MMU AP0362H2UL MMU AP0422H2UL ...
Page 15: ...15 2 2 Compact 4 Way Cassette Type MMU AP0071MH2UL MMU AP0091MH2UL MMU AP0121MH2UL ...
Page 16: ...16 MMU AP0151MH2UL MMU AP0181MH2UL ...
Page 156: ...156 MMU AP0152H2UL AP0182H2UL AP0212H2UL AP0242H2UL AP0302H2UL ...
Page 159: ...159 MMU AP0362H2UL AP0422H2UL ...
Page 168: ...168 11 3 Ceiling Type MMC AP0181H2UL AP0241H2UL AP0361H2UL AP0421H2UL ...
Page 174: ...174 MMK AP0153H AP0183H AP0243H ...