89
Check code
Location
of
detection
Description
System status
Error detection
condition(s)
Check items (locations)
Main
remote
controller
Outdoor 7-segment display
Check code
Sub-code
E08
E08
Duplicated
indoor address
Indoor
unit
I/F
Duplicated
indoor address
All stop
More than one indoor unit is
assigned same address.
• Check indoor addresses.
• Check for any change
made to remote controller
connection (group/
individual) since indoor
address setting.
E09
–
–
Remote
controller
Duplicated
master remote
controller
Stop of
corresponding
unit
In two remote controller
configuration (including
wireless), both controllers are
set up as master. (Header
indoor unit is shut down with
alarm, while follower indoor
units continue operating.)
• Check remote controller
settings.
• Check remote controller
P.C. boards.
E10
–
–
Indoor
unit
Indoor inter-
MCU
communication
error
Stop of
corresponding
unit
Communication cannot be
established/maintained upon
turning on of power or during
communication.
• Check for defect in indoor
P.C. board
E12
E12
01:
Indoor-outdoor
communication
02:
Outdoor-
outdoor
communication
I/F
Automatic
address starting
error
All stop
• Indoor automatic address
setting is started while
automatic address setting
for equipment in other
refrigerant line is in
progress.
• Outdoor automatic
address setting is started
while automatic address
setting for indoor units is in
progress.
• Perform automatic address
setting again after
disconnecting
communication cable to
that refrigerant line.
E15
E15
–
I/F
Indoor unit not
found during
automatic
address setting
All stop
Indoor unit cannot be
detected after indoor
automatic address setting is
started.
• Check connection of
indoor-outdoor
communication line.
• Check for error in indoor
power supply system.
• Check for noise from other
devices.
• Check for power failure.
• Check for defect in indoor
P.C. board.
E16
E16
00:
Overloading
01-:
No. of units
connected
I/F
Too many
indoor units
connected
All stop
• Combined capacity of
indoor units exceeds 125%
of combined capacity of
outdoor units.
Note:
If this code comes up
after backup setting for
outdoor unit failure is
performed, perform “No
overloading detected”
setting.
<“No overloading detected”
setting method>
Turn on SW09/Bit 2 on I/F
P.C. board of outdoor header
unit.
• More than 48 indoor units
are connected.
• Check capacities of indoor
units connected.
• Check combined HP
capacities of indoor units.
• Check HP capacity
settings of outdoor units.
• Check No. of indoor units
connected.
• Check for defect in outdoor
P.C. board (I/F).
Summary of Contents for Carrier MMC-AP0181H2UL
Page 12: ...12 MMU AP0152H2UL AP0182H2UL ...
Page 13: ...13 MMU AP0212H2UL MMU AP0242H2UL MMU AP0302H2UL ...
Page 14: ...14 MMU AP0362H2UL MMU AP0422H2UL ...
Page 15: ...15 2 2 Compact 4 Way Cassette Type MMU AP0071MH2UL MMU AP0091MH2UL MMU AP0121MH2UL ...
Page 16: ...16 MMU AP0151MH2UL MMU AP0181MH2UL ...
Page 156: ...156 MMU AP0152H2UL AP0182H2UL AP0212H2UL AP0242H2UL AP0302H2UL ...
Page 159: ...159 MMU AP0362H2UL AP0422H2UL ...
Page 168: ...168 11 3 Ceiling Type MMC AP0181H2UL AP0241H2UL AP0361H2UL AP0421H2UL ...
Page 174: ...174 MMK AP0153H AP0183H AP0243H ...