41
No.
8
9
10
11
12
Item
Recovery control for
cooling oil
(Refrigerant)
Recovery control for
heating refrigerant
(Oil)
Compensation
control for short
intermittent operation
Elimination of
retained heat
Display of filter sign
[ ]
(Not provided to the
wireless type)
∗
Separately set type
TCB-AX21UL is
prepared.
Outline of specifications
The indoor unit which is under STOP/Thermo-OFF
status or which operates in [FAN] mode performs the
following controls when it received the cooling oil
(Refrigerant) recovery signal from the outdoor unit.
1) Opens PMV of the indoor unit with a constant
opening degree.
2) Operates the indoor fan for approx. 3 minutes
during recovery control and after finish of control.
The indoor unit which is under STOP/Thermo-OFF
status or which operates in [FAN] mode performs the
following controls when it received the heating refrigerant
(Oil) recovery signal from the outdoor unit.
1) Opens PMV of the indoor unit with a constant
opening degree.
2) Stop the indoor fan.
1) For 3 minutes after start of operation, the operation
is forcedly continued even if the unit enters in
Thermo-OFF condition.
2) However the thermostat is OFF giving prior to
COOL/HEAT selection, ready for operation and
protective control.
1) When the unit stopped from [HEAT] operation, the
indoor fan operates with [L] for approx. 30 seconds.
1) The filter sign is displayed with LC by sending the
filter-reset signal to the remote controller when the
specified time (150H) elapsed as a result of integra-
tion of the operation time of the indoor fan.
2) The integrated timer is cleared when the filter-reset
signal is received from the remote controller.
In this time, if the specified time elapsed, the counted
time is reset and the LC display is deleted.
Remarks
• Recovery operation is
usually performed every
2 hours 5 minutes.
• The indoor unit which is
under thermo-OFF
(COOL) status or which
operates in [FAN] mode
stops the indoor fan and
displays [ ].
• Recovery operation is
usually performed every
1 hour.
(When there is even 1
indoor unit which the
thermo unit is off)
Usually the priority is given
to 5 minutes at outdoor
controller side.
[ FILTER] goes on.
Summary of Contents for Carrier MMC-AP0181H2UL
Page 12: ...12 MMU AP0152H2UL AP0182H2UL ...
Page 13: ...13 MMU AP0212H2UL MMU AP0242H2UL MMU AP0302H2UL ...
Page 14: ...14 MMU AP0362H2UL MMU AP0422H2UL ...
Page 15: ...15 2 2 Compact 4 Way Cassette Type MMU AP0071MH2UL MMU AP0091MH2UL MMU AP0121MH2UL ...
Page 16: ...16 MMU AP0151MH2UL MMU AP0181MH2UL ...
Page 156: ...156 MMU AP0152H2UL AP0182H2UL AP0212H2UL AP0242H2UL AP0302H2UL ...
Page 159: ...159 MMU AP0362H2UL AP0422H2UL ...
Page 168: ...168 11 3 Ceiling Type MMC AP0181H2UL AP0241H2UL AP0361H2UL AP0421H2UL ...
Page 174: ...174 MMK AP0153H AP0183H AP0243H ...