137
No.
d
Part name
Electric parts
assembly
Procedures
1) Perform work of item
c
.
2) Take off PMV cover fixing screws (2 pcs.)
and then remove PMV cover.
3) Take off drain guide fixing screws (2 pcs.)
and then remove the drain guide.
4) Take off earth screw (1 pc.) fixed to the
end plate.
5) Pull out TC1, TC2 and TCJ sensors from
the sensor holder of the heat exchanger.
(When reassembling the electric parts, be
careful to the attaching positions of every
sensor. TC2 and TCJ sensors resemble in
the shapes, so distinct them by marking,
etc. when mounting them.)
6) Take off the connector cover mounting
screw (1 pc.) and then remove the
connector cover.
7) Take off the clamp base mounting screw
(1 pc.) and then remove the clamp base.
8) Remove the bundling band and then
remove the fan motor connector (5P), the
connector (5P) for louver motor and the
connector (6P) for PMV motor from the
P.C. board.
(When mounting the P.C. board, fix the
lead wires again by the bundling band.)
Tighten the bundling band at the same
position before removing.)
9) Disengage the display unit by simply
pushing at the top of the display unit.
10) Remove the fixing screw that secures
the electric parts box assembly, LED
assembly and remove the assembly.
Same as reassembly pace Addition of the
following cautions
<Cautions in reassembling>
Mount the electric parts box to the main unit
in the reverse order to the removing procedure.
Determine the sensor positions and lead
wire drawing as same as those before
removing according to the figure.
Remarks
PMV cover
PMV cover
PMV cover
Connector cover
fixing screw
PMV cover fixing screw
PMV cover fixing screw
Drain guide
Drain guide
Drain guide
fixing screw
fixing screw
Connector cover
Connector cover
Earth screw
Earth screw
TC2 sensor
TC2 sensor
(0.24"(6mm))
(0.24"(6mm))
TC1 sensor (0.16"(4mm))
TC1 sensor (0.16"(4mm))
TCJ sensor
(0.24"(6mm) sleeve provided))
Fan motor connector
Fan motor connector
Binding band
Binding band
PMV connector
PMV connector
Fixing screw
Fixing screw
PMV cover fixing screw
Drain guide
fixing screw
Connector cover
Earth screw
TC2 sensor
(0.24"(6mm))
TC1 sensor (0.16"(4mm))
Fan motor connector
Binding band
PMV connector
Fixing screw
Clamp base
Clamp base
Clamp base
Summary of Contents for Carrier MMC-AP0181H2UL
Page 12: ...12 MMU AP0152H2UL AP0182H2UL ...
Page 13: ...13 MMU AP0212H2UL MMU AP0242H2UL MMU AP0302H2UL ...
Page 14: ...14 MMU AP0362H2UL MMU AP0422H2UL ...
Page 15: ...15 2 2 Compact 4 Way Cassette Type MMU AP0071MH2UL MMU AP0091MH2UL MMU AP0121MH2UL ...
Page 16: ...16 MMU AP0151MH2UL MMU AP0181MH2UL ...
Page 156: ...156 MMU AP0152H2UL AP0182H2UL AP0212H2UL AP0242H2UL AP0302H2UL ...
Page 159: ...159 MMU AP0362H2UL AP0422H2UL ...
Page 168: ...168 11 3 Ceiling Type MMC AP0181H2UL AP0241H2UL AP0361H2UL AP0421H2UL ...
Page 174: ...174 MMK AP0153H AP0183H AP0243H ...