149
2. Every pushing [Unit, Louver
UNIT LOUVER
] button, the indoor unit address in the group are displayed successively.
2
Specify the indoor unit No. to be replaced.
3. Using the set temperature
/
buttons, the CODE No. (DN) can be moved up and down one by one.
3
4. First change the CODE No. (DN) from
10
10
10
10
10
to
01
01
01
01
01
. (Setting of filter sign lighting time)
Make a note of the set data displayed in this time.
5. Next change the CODE No. (DN) using the set temperature
/
buttons.
Also make a note of the set data.
6. Repeat item 5. and made a note of the important set data as shown in the below table.
∗
01
01
01
01
01
to
AA
AA
AA
AA
AA
are provided in the CODE No. (DN). On the way of operation, DN No. may skip.
7. After finishing making a note, push
TEST
button to return to the usual stop status.
4
(Approx. 1 minute is required to be able to use the remote controller.)
Minimum requirements for CODE No.
Capacity of the indoor unit is necessary to set
the revolutions of the fan.
Procedure2: Replacement of service P.C. board
1. Replace the P.C. board with a service P.C. board.
In this time, setting of jumper line (cut) or setting of DIP switch on the former P.C. board should be reflected
on the service P.C. board. Refer to the following table about DIP switch setting and drawing of P.C. board
parts layout.
2. It is necessary to set Indoor unit to be exchanged : Remote controller = 1 : 1
Based upon the system configuration, turn on power of the indoor unit with one of the following items.
1) Single (Individual) operation
Turn on power of the indoor units and proceed to
Procedure 3
2) Group operation
A) In case that power of the exchanged indoor unit only can be turned on.
Turn on power of the exchanged indoor unit only and proceed to
Procedure 3
B) In case that power of the indoor units cannot be turned on individually. (
CASE 1
)
a) Remove temporarily the group wire connected to the terminal blocks A and B of the exchanged
indoor unit.
b) After connecting the remote controller wire only to the removed terminal block, turn on power of
the indoor units and proceed to
Procedure 3
* When the above methods cannot be used, follow at the
CASE 2
below.
DN
11
12
13
14
Contents
Indoor unit capacity
Refrigerant line address
Indoor unit address
Group address
4
3
1
2
TEMP.
ON / OFF
SET
TIME
TEST
FILTER
RESET
CL
SAVE
SWING/FIX
VENT
UNIT LOUVER
CODE No.
UNIT No.
R.C. No.
TIMER SET
MODE
FAN
SET DATA
SETTING
Summary of Contents for Carrier MMC-AP0181H2UL
Page 12: ...12 MMU AP0152H2UL AP0182H2UL ...
Page 13: ...13 MMU AP0212H2UL MMU AP0242H2UL MMU AP0302H2UL ...
Page 14: ...14 MMU AP0362H2UL MMU AP0422H2UL ...
Page 15: ...15 2 2 Compact 4 Way Cassette Type MMU AP0071MH2UL MMU AP0091MH2UL MMU AP0121MH2UL ...
Page 16: ...16 MMU AP0151MH2UL MMU AP0181MH2UL ...
Page 156: ...156 MMU AP0152H2UL AP0182H2UL AP0212H2UL AP0242H2UL AP0302H2UL ...
Page 159: ...159 MMU AP0362H2UL AP0422H2UL ...
Page 168: ...168 11 3 Ceiling Type MMC AP0181H2UL AP0241H2UL AP0361H2UL AP0421H2UL ...
Page 174: ...174 MMK AP0153H AP0183H AP0243H ...