Function to clear error
1. Clearing method from remote controller
~
How to clear error of outdoor unit
In the unit of refrigerant line connected by indoor unit of the remote controller to be operated, the error of
the outdoor unit currently detected is cleared. (Error of the indoor unit is not cleared.)
The service monitor function of the remote controller is utilized.
<Method>
1
Push
CL
+
TEST
buttons simultaneously for 4 seconds or more to change the mode to service
monitor mode.
2
Push
TEMP.
button to set the item code to [FF].
3
The display of A part in the following figure is counted as “
0005
0005
0005
0005
0005
”
→
→
→
→
→
“
0004
0004
0004
0004
0004
”
→
→
→
→
→
“
0003
0003
0003
0003
0003
”
→
→
→
→
→
“
0002
0002
0002
0002
0002
”
→
→
→
→
→
“
0001
0001
0001
0001
0001
”
→
→
→
→
→
“
0000
0000
0000
0000
0000
” with 5-seconds interval.
When “
0000
0000
0000
0000
0000
” appear, the error was cleared.
∗
However counting from “
0005
” is repeated on the display screen.
4
When pushing
TEST
button, the status becomes normal.
~
How to clear error of indoor unit
The error of indoor unit is cleared by
ON / OFF
button of the remote controller.
(Only error of the indoor unit connected with remote controller to be operated is cleared.)
1 2 3 4
Returns to normal status
<Operation procedure>
4
3
2
1
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
Summary of Contents for Carrier MMC-AP0181H2UL
Page 12: ...12 MMU AP0152H2UL AP0182H2UL ...
Page 13: ...13 MMU AP0212H2UL MMU AP0242H2UL MMU AP0302H2UL ...
Page 14: ...14 MMU AP0362H2UL MMU AP0422H2UL ...
Page 15: ...15 2 2 Compact 4 Way Cassette Type MMU AP0071MH2UL MMU AP0091MH2UL MMU AP0121MH2UL ...
Page 16: ...16 MMU AP0151MH2UL MMU AP0181MH2UL ...
Page 156: ...156 MMU AP0152H2UL AP0182H2UL AP0212H2UL AP0242H2UL AP0302H2UL ...
Page 159: ...159 MMU AP0362H2UL AP0422H2UL ...
Page 168: ...168 11 3 Ceiling Type MMC AP0181H2UL AP0241H2UL AP0361H2UL AP0421H2UL ...
Page 174: ...174 MMK AP0153H AP0183H AP0243H ...