40
Toshiba
The address switch setting of the digital input / output relay interface does not match that in the setting file.
13-4-8. Communication error with the energy monitoring relay
interface is displayed.
13-5.Questions about Functions
8
Noise is superposed on the communication wiring.
Check the waveform between RS-485 communication wiring A and B.
If noise is superposed, identify the noise source and remove it.
9
The communication cable in use is not the specified
one. (Wire diameter is smaller)
Change it to the specified communication cable.
No.
Cause
Solution
3
The RS-485 wiring is defective between the digital input
/ output relay interface and the controller.
1.Check the address switch setting of the digital input / output relay
interface and the setting in the setting file.
2.Check if the RS-485 LED (Green) of the digital input / output relay
interface blinks.
No.
Cause
Solution
1
The energy monitoring relay interface is not turned on. Check if the “POWER” LED of the energy monitoring relay interface
illuminates.
2
The address switch setting of the energy monitoring
relay interface does not match that in the setting file.
1.Check the address switch setting of the energy monitoring relay
interface and the setting in the setting file.
2.Check if the RS-485 LED (Green) of the energy monitoring relay
interface blinks.
No.
Questions
Answer
1
What is the procedure to create a setting file?
Please read the Owner’s manual of the Setting File Creation Software.
2
How many air conditioners can be connected?
Up to 128 units of air conditioners can be connected. Note that up to 64 units
can be connected per TCC-LINK line.
3
How many air conditioners can be connected?
Up to 64 units can be connected per TCC-LINK line. The controller has two
TCC-LINK lines, thus up to 128 units can be connected.
4
How many central remote controllers can be
connected?
Up to 10 central remote control devices can be connected per TCC-LINK line.
The central control devices include a central remote controller, a schedule
timer, and an ON / OFF controller.
5
Is it possible to turn on or off the lighting equipment, fan
or any other manufacture’s air conditioner?
This is possible by connecting to the general devices control interface.
6
Can a schedule timer be used together?
Possible. Note that schedule must be set so that it does not conflict with the
schedule setting from the browser.
7
Can a touch screen-type air conditioning management
system be used together?
Not possible. However, it is possible to use a touch screen-type air
conditioning management system together with a central control device other
than the Web-based central remote controller.
8
Can the BACnet system be used together?
Not possible. However, it is possible to use BACnet system together with a
central control device other than the Web-based central remote controller.
9
Can the LONwork system be used together?
Possible. Check that it works.
10
Can a remote monitoring system be used together?
Not possible. However, it is possible to use a remote monitoring system
together with a central control device other than the Web-based central
remote controller.
11
Can a device in the AI-NETwork series be connected? Not possible. Use an air conditioning management system supported for the
AI-NETwork series.
12
Up to how many PCs can be connected?
Up to 4 users can simultaneously log on.
Up to 4 PCs can be simultaneously connected.
Without simultaneous connection, the number of PCs connected has no
limitation.
13
How many users can simultaneously access the
system?
14
Can the system connect to an intra-company LAN?
Possible. However, check with your network administrator if the connection
is available.
No.
Cause
Solution
+00A10-026_01EN.book Page 40 Monday, February 14, 2011 2:46 PM