Termination
The termination switches for TCC-LINK are placed in the central controller box. Detach the panel when configuring
termination setting.
NOTE
TCC-LINK connection is terminated on indoor units. Set SW 200 to “Open” for both TCC-LINK 1 and 2.
1
ON
OFF
2 3 4
DS25
<1> Always OFF
• Always set this bit to OFF.
<4> Fire alarm input switching (Set this switch to match the fire alarm input connection set in chapter 4.)
Set OPEN or CLOSE input junction pegged to fire alarm.
• OFF: Set CLOSE input junction pegged to fire alarm.
• ON: Set OPEN input junction pegged to fire alarm.
COM-DI
DI3
COM-DI
DI3
(Fire alarm)
(Normal)
COM-DI
DI3
COM-DI
DI3
(Fire alarm)
(Normal)
Factory setting: All OFF
<2> Synchronization of zone setting data
OFF: With synchronization
ON: Without synchronization
This bit specifies whether to perform synchronous communication of zone setting
data between Smart Managers.
* When this bit is set to ON (without synchronization), synchronous communication
is not performed, and when zone setting is made, the data is not reflected in other
Smart Managers.
<3> Always OFF
• Always set this bit to OFF.
<DS25>
ON
SW200
SW200
TCC-LINK termination switches
TCC-LINK1
Open
TCC-LINK1
100
Ω
TCC-LINK2
Open
TCC-LINK2
Open
TCC-LINK1
Open
TCC-LINK1
100
Ω
TCC-LINK2
100
Ω
TCC-LINK2
100
Ω
1
ON
2
1
ON
2
1
ON
2
1
ON
2