PLACE OF INSTALLATION
SUNDAY 30/130 B
boilers can be installed in any indoor
location provided the flue gases are adequately removed
and comburent air drawn in from outdoors. Provided the
boiler is properly installed, the boiler room itself does not
need any ventilation as such, since the combustion cir-
cuit of
SUNDAY 30/130 B
boilers is sealed with respect
to the environment. If instead comburent air is drawn
from inside the boiler room itself, the room must have
adequately dimensioned ventilation conforming to the
relevant technical standards.
IMPORTANT
Before installing the boiler, thoroughly flush out all the
pipes to remove any dirt and deposits that could compro-
mise the correct functioning of the boiler.
Before lighting the burner for the first time, make sure
that the boiler is configured for use with the type of
gas supplied. The type of gas is specified on the pack-
aging label and on the gas identification plate on the
boiler itself.
b
When installing the boiler, allow sufficient space
around it to access all safety and control devices
and to permit easy maintenance.
b
Make sure that the boiler’s index of electrical pro-
tection is adequate for the characteristics of the
room where it is to be installed.
b
If the specific weight of the gas supply to the burner
is greater than the specific weight of air, all electrical
parts must be installed at least 500 mm above floor
level.
a
SUNDAY 30/130 B
boilers must be installed indoors.
They are not designed for outdoor use and are not
fitted with automatic frost protection devices.
≥ 50 cm
≥ 50 cm
≥ 100 cm
≥ 20 cm
60 cm
154 cm
61 cm