13
Install 1/2” non-insulated PEX pipe between a drain (the drain can be in the garage or
mechanical room since the unit is equipped with a condensate pump) and the outlet of
the
RC4LT
unit.
Install an elbow at the
RC4LT
location as in step B’. It is best to connect the other end
of the tube to an open drain (e.g. floor drain) to prevent the risk of odor coming from
the sewers in the wine cellar. Connecting to a drain using a ‘’P-trap’’ principle to prevent
odors is not effective, as the system may never generate condensation if the humidity
in the house is well managed, the ‘’ P-trap’’ would thus end up drying up.
C
2’’-6’’
[50-150]
At the ceiling in the wine cellar, leave between 2” and 6” of tubing hanging from the ceil-
ing and install an elbow on each conduit.
B’
NOTE :
It is preferable not to exit all the tubes at the same height to facilitate the
connection of the system during its final installation. It is also possible to hang lon-
ger tubes at this stage and install the elbows only during the final installation of the
RC4LT
after the walls are closed.
NOTE :
To bring the conduits out of the wall in the mechanical room in an aesthetic
way, it is possible to use a low voltage 2-gang wall bracket.