Texmate Tiger 380 Series Programming Manual Download Page 12

12

2 February, 2005   Code Sheet V4.01d (NZ1001)

Follow These  Steps

The following procedures are written for SP1, all other setpoints are con-
figured in a similar manner.

1) Press the 

and 

buttons at the same time. This enters the set-

point programming mode.The display toggles between [SP_1] and
[18000].

This is SP1 of the 

Setpoint Activation Values Mode

. Use the 

and 

buttons to set SP1 or the 

button to move to the required

setpoint.

2) After all required setpoint 

activation values

have been set, press

the 

button until [SPC_1] appears. This is the  

Setpoint & Relay

Control Settings Mode

.

SPC_1 is the 

setpoint and relay control settings

programming

menu for SP1. Set the three digits according to the codes in the

Setpoint and Relay Control Function Settings 

opposite in the fol-

lowing order:

Third Digit – Setpoint Delay Mode 

Set to [XX5] and program the hysteresis, deviation, or PID
functions as required for SP1.

Reset back to [XX0].

Third Digit – Setpoint Timer Mode

Set to [XX6] and program the timer mode functions as
required for SP1.

Reset back to [XX0].

Third Digit – Setpoint Reset & Trigger Functions

Set to [XX7] and program the reset and trigger functions as
required for SP1.

Reset back to [XX0].

Second Digit – Setpoint Activation Source Mode

Set to [X1X] to select the setpoint activation source for SP1
from any channel or selected register shown above. Reset
back to [X0X].

If the SP source is from an external digital input, set to one of
either [X2X] to [X7X] to select the setpoint activation source
from one of six digital inputs (2 to 7).

See *Note at 2nd digit.

First Digit – Relay Energize Mode

Select the relay energize mode for SP1 from 0 to 3.

Third Digit – Relay Latching & Manual Reset Functions

Program the third digit setpoint relay latching and manual
reset functions between 0 to 4 as required.

3) Press the 

button to move to move to [SPC_2].

4) Repeat Step 2 for all required setpoints.

Setpoint Setup Sequence

0 No 

Latching

1  Relay Latched ON
2  Manual Relay Reset
3  Relay Latched and Manual Relay

Reset

4  Relay Latched Off

5  Mode: Hysteresis, Deviation, PID,

SP Flashing, SP Tracking

6 Timer 

Modes:

• OFF
• Normal Delay
• Repeat ON
• Pulse ON
• 1-Shot ON
• Repeat OFF
• Pulse OFF
• 1-Shot OFF

Note:

In PID Mode, all Timer Modes on
SP1 set in [XX6] are not functional.

7  Advanced Functions Mode:

• OFF.
• Reset Trigger.
• Reset Destination.
• Reset Mode.
• Reset Constant.
• Trigger Print from SP.
• Trigger Log from SP.

Note:

[XX5], [XX6], and [XX7] are set up
procedures only. To finish, reset to
0-4 as required for setpoint latching
and relay reset modes.

SETPOINT PROGRAMMING MODE – SPC_1 to SPC_6

Relay Energize Function

0 Relay energizes ABOVE setpoint value

1  Relay energizes BELOW setpoint value

2  Relay energizes AT OR ABOVE setpoint value with FALLING INPUT

SIGNAL INITIAL START-UP INHIBIT

3 Relay energizes BELOW setpoint value with RISING INPUT SIGNAL

INITIAL START-UP INHIBIT

See Page 15 for a detailed description of the relay energize options.

SP Activation Source

Activate Setpoint Source from
Selected Register

1  Select Data Source for Setpoint

Note:

[X1X] is a register selection procedure
only. To finish, reset to [X0X] to activate
the selection, or reset to 2-7 as required
for digital input selection.

2 Digital 

Input 

– Capture Pin

3 Digital 

Input 

– D1 (selected input modules)

4 Digital 

Input 

– D2 (selected input modules)

5 Digital 

Input 

– D3 (selected input modules)

6 HOLD Pin
7 LOCK Pin

*Note:

If the setpoint source is set to [oFF] or a
digital input, the setpoint activation value
will have no effect and will not be dis-
played.

SP Functions

FIRST DIGIT

SECOND DIGIT

THIRD DIGIT

SETPOINT AND RELAY CONTROL FUNCTION SETTINGS

Go to
Page 13

Go to
Page 13

Go to
Page 14

Select Source for Setpoint Functions

[TARE]

[RESULT]

[DISP]

The button
takes you forward.

[VALY_1]

[PEAK_1]

[AUX_1] to [AUX_16]

Constant pressure on the 

button

moves thru Registers 111 to 16383
one register at a time.

Note, not all registers between 111
and 16383 are available.

Use the 

and 

buttons to cycle thru the

Registers Menu and Registers (111 to 16383)
to select the data source for displays, peak and
valley, totalizers, and analog output.

Registers [  111] to [16383]

[TOT_1] to [TOT_6]

[CH_1] to [CH_7] 

[VALY_2]

[PEAK_2]

[VALY_3]

[PEAK_3]

The

button

takes you back.

Summary of Contents for Tiger 380 Series

Page 1: ...isplay text editing Configuration data copying Downloading macros to the meter Tamper proof settings Tiger 380 Series controllers except the DI 802 have tamper proof lockout switches to prevent users...

Page 2: ...e holding both buttons press the Prog button then release all three buttons Press and hold the and buttons Programming Tip The Model and Software Code Version check ing procedure can be performed at a...

Page 3: ...n the controller is powered up Macros can be installed in the controller at the factory during initial programming or by the cus tomer at some later date Macros are written and compiled using the Tige...

Page 4: ...put pins on the rear of the con troller Display test pin Hold pin Lock pin The Setpoint and Relay Control Settings diagram on Pages 12 to 14 shows the three digit configuration settings that are appli...

Page 5: ...Port 2 3 Port 3 Converting F to C See User Notes on Page 21 for a procedure See CH1 Thermocouple Calibration on Page 21 for a procedure See CH1 RTD Calibration on Page 22 for a procedure CHANNELS 5 6...

Page 6: ...t input module data sheet for setup procedures Use buttons to set CAL_LO Use buttons to set CAL_HI 0 Manual Calibration requires NO input source 1 2 point Calibration requires dual input source 2 Cali...

Page 7: ...signal channel must be selected in the 3rd digit when configuring a lin earization table using the auto setup mode 0 1 CH1 2 CH2 3 CH3 4 CH4 5 CH5 6 CH6 7 CH7 THIRD DIGIT THIRD DIGIT THIRD DIGIT Use...

Page 8: ...NDARY display is the bargraph display Note 3 These functions are only available on selected input modules Note 4 If Code 1 s display modes have been entered second digit set to 5 6 or 7 the display wi...

Page 9: ...r 2 2 Output Register 3 3 Output Register 4 4 Output Register 5 5 Output Register 6 6 Output Register 7 7 Smart Input Module Register 1 Code Setup See Note 6 THIRD DIGIT FIRST DIGIT SECOND DIGIT CODE...

Page 10: ...1 Frequency 999 99 Hz range from 0 01 Hz 2 Frequency 99 999 kHz range from 1 Hz 1 s gate 3 Frequency 500 kHz range from 10 Hz 0 1 s gate 4 Pulse 50 0000 s 100 s resolution 5 Period 999 99 ms 10 s reso...

Page 11: ...ear FIFO Buffer 3 Reset Buffer Number to 0 Note Setting Code 8 to 3XX resets the data log buffer to 0 Once reset Code 8 must be set back to the required data log buffer setting DATE TIME STAMP OPTIONS...

Page 12: ...Relay Reset 4 Relay Latched Off 5 Mode Hysteresis Deviation PID SP Flashing SP Tracking 6 Timer Modes OFF Normal Delay Repeat ON Pulse ON 1 Shot ON Repeat OFF Pulse OFF 1 Shot OFF Note In PID Mode al...

Page 13: ...o 6553 5 65 535 secs On_t 0 1 0 001 to 6553 5 65 535 secs Off time oFF_t 0 1 0 001 to 6553 5 65 535 secs Off time oFF_t 0 1 0 001 to 6553 5 65 535 secs Minimum off time M_of 0 1 to 6553 5 secs Set Up...

Page 14: ...ct reset trigger from 1 of 4 relay operating edges Reset Trigger Select register to be reset Reset Destination Register Select Reg in reset mode Reset Mode Copy contents of selected register SP1 to SP...

Page 15: ...ble CONST This mode stores a user defined constant into the selected destination regis ter In most cases this number will be zero but it can be any number I S C This mode stores the current input valu...

Page 16: ...nual Calibration 2 point Calibration INPUT INPUT 111 ZERO SPAN INPUT INPUT 112 ZERO SPAN INPUT INPUT 113 ZERO SPAN INPUT INPUT 114 ZERO SPAN INPUT INPUT 025 SPAN 035 ZERO SPAN 045 CHANNEL 055 CHANNEL...

Page 17: ...Analog Output 152 CAL LOW CAL HIGH OUTPUT OUTPUT SOURCE SOURCE 1st DIGIT 2nd DIGIT 3rd DIGIT SUB SETTINGS TC TYPE UNITS TC TYPE UNITS TC TYPE UNITS 121 ZERO SPAN INPUT INPUT Calibrate RTD 122 ZERO SPA...

Page 18: ...IGIT CODE 4 PRESCALER 1st DIGIT 2nd DIGIT 3rd DIGIT CODE 5 SMART INPUT MODULE SETTINGS 1st DIGIT 2nd DIGIT 3rd DIGIT CODE 6 SMART INPUT MODULE SETTINGS 1st DIGIT 2nd DIGIT 3rd DIGIT CODE 7 1st DIGIT 2...

Page 19: ...ING SPAN PB INT DER ARW MCT SP TRACKING SPAN PB INT DER ARW MCT SP TRACKING TIMER MODE SETTINGS SPC_1 _ _ 6 SPC_2 SPC_3 SPC_4 SPC_5 SPC_6 _ _ 6 _ _ 6 _ _ 6 _ _ 6 _ _ 6 SPC SETTING NORMALLY OFF PULSED...

Page 20: ...setpoint with the contents of a selected source register Setpoint Control Settings XX7 Select the contents of one register to be copied into another register by a setpoint The 38 named registers that...

Page 21: ...he Calibration mode CAL set to 111 and fine tune the thermocouple calibration over the required temperature range Fine Tune Calibration over Specific Temperature Range Follow Steps 1 to 5 for setting...

Page 22: ...ls 2 and 3 using the following settings CH2 Code 4 210 for type 385 CAL 132 to calibrate type 385 Code 4 2X0 to select specific RTD CAL 112 to fine tune selected RTD CH3 Code 5 X31 for type 385 CAL 13...

Reviews: