Autotransformers (3 phase and single-phase)
Contrary to the two-winding transformer the windings of an autotransformer can not be separated.
The winding of an autotransformer is a combination of the high- and low-voltage windings (HV and
LV, see figure below).
For testing the insulation of an autotransformer all seven bushings (three bushings for a single-phase
unit) have to be connected together (HV1+HV2+HV3+LV1+LV2+LV3+0).
For a conventional autotransformer without a tertiary winding only an overall test to ground can be
performed (C
HG
).
If an autotransformer is equipped with a tertiary winding which is accessible, the test procedure is
exactly the same as described in section “Two Winding Transformer”.
Measurement connections of an autotransformer with tertiary winding for measurement of C
HG
& C
HT
Test Connections
Seq.line
DUT
INPUT A
to
INPUT
HV GND
to
Test Mode
High Voltage
to
1
C
HT
T
Tank GND
UST A
HV+LV+0
2
C
HG
T
Tank GND
GST gA+B
HV+LV+0
3
C
TG
HV+LV+0
Tank GND
UST A
T
4
C
TG
+ C
HG
-
Tank GND
GST gA+B
HV+LV+0+T
Note: Test line #4 can be used to inter-check the measurement results. (#4 = #2 + #3). Additional
measurements in other test modes can be executed to inter-check the measurements results.