Applications Guide
121
Two Winding Transformers (3 phase and single-phase)
Measurement connections of a two windings transformer for measurement of C
HG
and C
HL
Test Connections
Sequence
Line
DUT
INPUT A
to
INPUT
HV GND
to
Test Mode
High Voltage
to
1
C
HL
LV
Tank GND
UST A
HV
2
C
HG
LV
Tank GND
GST gA+B
HV
3
C
LG
HV
Tank GND
GST gA+B
LV
4
C
LG
+ C
HG
-
Tank GND
GST gA+B
LV + HV
Note: Test line #4 can be used to inter-check the measurement results. (#4 = #2 + #3). Additional