11.3 Power expansion by SMA battery inverter
System with
one
Sunny Island (single-phase)
System with
three
Sunny Islands (3-phase)
The charging and discharging capacity can be increased by increasing the number of Sunny Islands. The number of Sunny Islands is
increased in steps of 3.
1, 3, 6, 9 and 12 Sunny Islands
can be operated in grid-parallel mode.
If more than one Sunny Island is connected to the battery, a battery fuse unit
(Bat Fuse)
must be connected between the Sunny
Islands and the battery. This ensures that electricity is distributed to the Sunny Islands via fuse elements. In a cluster comprising
three Sunny Islands, one Sunny Island will serve as the Master, which will control the other two Sunny Islands as Slave 1 and Slave 2.
Max. 3.3 kW 1 x SI 4.4M
Max. 4.6 kW 1 x SI 6.0H
Charge/Discharge power per
Cluster
Max. 4.6 kW 1 x SI 8.0H
Charge/Discharge power per
Cluster
Max. 9.9 kW 3 x SI 4.4M
Max. 13.8 kW 3 x SI 6.0H
Max. 18.0 kW 3 x SI 8.0H
On-Grid expandable up to 4 clusters.
23
www.tesvolt.com
E.IA. .ENG-
TS
A.11
Summary of Contents for TS25