Position
A
Description/note
Designation
AC power cable
Connection to AC2 Gen/Grid Terminals L, NTT and PE
Connection to the public mains grid via a 3-core cable
Conductor cross-section: 6 mm² … 16 mm²
Battery connection:
Conductor cross-section: 50 mm² ... 120 mm²
Cable diameter: 14 mm ... 25 mm
Tightening torque: 12 Nm
cabel DC –
cabel DC +
B
C
E
Speedwire network cable
Connection ComETH
F
Data cable to Lithium-Ion
battery
ComSync In connection
Connection for the Lithium Ion Battery Management System
The communication bus must be connected to the
Lithium-Ion battery and the termination resistor must be
plugged into the ComSync Out connection.
E.IA. .ENG-
TS
A.11