31
ENG
supply to equipment during servicing, then a permanently operating form of leak detection shall be located at
the most critical point to warn of a potentially hazardous situation.
2. Particular attention shall be paid to the following to ensure that by working on electrical components, the
casing is not altered in such a way that the level of protection is affected. This shall include damage to cables,
excessive number of connections, terminals not made to original specification, damage to seals, incorrect
fitting of glands, etc.
Ensure that apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of
preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the
manufacturer’s specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment.
Intrinsically safe components do not have to be isolated prior to working on them.
18.
Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not
exceed the permissible voltage and current permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on while live in the presence of a
flammable atmosphere. The test apparatus shall be at the correct rating.
Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of
refrigerant in the atmosphere from a leak.
19.
Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any
other adverse environmental effects. The check shall also take into account the effects of aging or continual
vibration from sources such as compressors or fans.
20.
Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or detection of
refrigerant leaks. Ahalide torch (or any other detector using a naked flame) shall not be used.
21.
Leak detection methods
The following leak detection methods are deemed acceptable for systems containing flammable refrigerants.
Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be
adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.)
Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak
detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the
refrigerant employed and the appropriate percentage of gas (25 % maximum) is confirmed.
Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine
shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work.
If a leak is suspected, all naked flames shall be removed/ extinguished.
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the
system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Oxygen free
nitrogen (OFN) shall then be purged through the system both before and during the brazing process.
22.
Removal and evacuation
When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures
shall be used. However, it is important that best practice is followed since flammability is a consideration. The
following procedure shall be adhered to:
- Remove refrigerant;
- Purge the circuit with inert gas;
- Evacuate;
- Purge again with inert gas;
-Open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed
with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or
oxygen shall not be used for this task.
Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the
working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process
shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall
be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if
brazing operations on the pipe-work are to take place.
Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation
available.
23.
Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment
Summary of Contents for TT26X71-0932IA
Page 33: ...33 BG 4A 250V III 50 cm 8...
Page 34: ...34 BG...
Page 35: ...35 BG No 1 2 3 4 LED 5 6 7 8 9 10 11 12 No 13 14 15 16 17...
Page 36: ...36 BG No Led 1 SLEEP SLEEP 2 1 Timer 2 3 TIMER Timer COOL 3 HEAT 5 COOL...
Page 40: ...40 BG 1 2 3 4 1m flashing swing 1 1 2 deactivate 2 2 2 1 2 deactivate flashing 3 2 2 Fan...
Page 47: ...47 BG 10Pa 5g 10g A 5 B 10 C D A B 22 R290 R161 R410A 32 Water drain pipe...
Page 48: ...48 BG mm 250cm...
Page 49: ...49 BG 1 65 2 1 2 3 4 PCB 1 2 32mm 3 4 5...
Page 50: ...50 BG 3 1 3 1 2 3 4 R32 R290 1 2 3 4 1 2...
Page 51: ...51 BG 1 2 3 4 1 25mm 2 1 2 3 4 5 6 1...
Page 53: ...53 BG 1 2 3 4 ON OFF FAN MODE TIMER 6 1 4 7 7 1 2 8 1 8 8 t...
Page 57: ...57 BG 6 N B LCD 1 2 3 45 C 4 5 1 2 40 3 1 2 3...
Page 58: ...58 BG TIMER ON LIGHT...
Page 59: ...59 BG IPM PCB EEPROM 1 2 4m2 3 4 4m2 5 6 7 8 9 10 11 12 13 14 15...
Page 60: ...60 BG 16 1 2 3 4 5 CO2 6 7 8 9 17 1...
Page 61: ...61 BG 2 18 19 20 21 LFL 25 OFN 22 OFN OFN OFN...
Page 62: ...62 BG 23 a b c d e f g h 80 i j k 24 25...
Page 64: ...64 24 13 12 TESLA 1 2 2 1 2 2 TESLA 2 3 2 4 2 5 2 6 2 7 2 8 2 9 2 10 2 11...
Page 65: ...65 2 12 3 4 5 6 7 8 112 115 119 112 1 2 1 2 3 113 1 2 3 2 114 4 5 114 1 113 1 2 2 3...
Page 66: ...66 115 4 115 1 2 1 3 1 1 10 02 9700970 02 9700971 9 30 19 00 10 00 16 00...
Page 67: ...67...
Page 68: ...68 GR 4A 250V H 50 cm 8...
Page 69: ...69 GR...
Page 70: ...70 GR 1 2 3 4 LED 5 6 7 8 9 10 11 12 13 14 15 16 17...
Page 71: ...71 GR 1 SLEEP 2 1 2 3 3 5...
Page 73: ...73 GR HEALTH 3 Ap 1 2 3 4 AUTO 5 COOL 6 DRY 7 FAN 8 HEAT 9 ECO ECO...
Page 75: ...75 GR 1 2 3 4 1 m 1 1 2 2 2 2 t 1 2 2 2...
Page 76: ...76 GR FAN MODE COOL 1 2 3 MODE HEAT 1 2 3 MODE DRY MODE FAN MODE AUTO 2 10...
Page 82: ...82 GR 10 Pa 5 g 10 g A 5 B o 10 A B R22 R290 R161 R410A R32...
Page 83: ...83 GR mm 250 cm...
Page 84: ...84 GR 1 65 2 1 2 3 4 1 2 32 mm 3 4 5...
Page 85: ...85 GR 3 1 3 1 2 3 4 R32 R290 1 2 3 4 1 2 NAI OXI NAI OXI OXI...
Page 86: ...86 GR 1 2 3 4 1 25 mm 2 1 2 3 4 5 6 1 1...
Page 88: ...88 GR 1 2 3 4 MODE 3 2 3 6 1 4 7 7 1 2 8 1 8 8...
Page 92: ...92 GR 6 LCD 1 2 3 45 oC 4 5 1 2 40 C 3 1 2 3...
Page 93: ...93 GR...
Page 94: ...94 GR IPM EEPROM 1 2 4 m2 3 4 4 m2 5 6 7 8 9 10 11 12 13 14 15...
Page 95: ...95 GR 16 1 2 3 4 5 CO2 6 7 8 9...
Page 96: ...96 GR 17 1 2 18 19 20 21 LFL 25 OFN 22 OFN...
Page 97: ...97 GR OFN OFN 23 80 24 25...
Page 99: ...99 TESLA 8 9 TESLA email warranty gr comtrade com...
Page 100: ...100 1 Service 2 Service 3 Service 4 Service 5 Service 6 Service 7 Service 8 Service 9 Service...
Page 270: ...www tesla info...