30
ENG
16.
Information on servicing
:
1. Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure
that the risk of ignition is minimized. For repair to the refrigerating system, the following precautions shall be
complied with prior to conducting work on the system.
2. Work procedure
Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or
vapour being present while the work is being performed.
3. General work area
All maintenance staff and others working in the local area shall be instructed on the nature of work being
carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off.
Ensure that the conditions within the area have been made safe by control of flammable material.
4. Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the
technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being
used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe
5. Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire
extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to
the charging area.
6. No ignition sources
No person carrying out work in relation to a refrigeration system which involves exposing any pipe work shall
use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition
sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing,
removing and disposal, during which refrigerant can possibly be released to the surrounding space. Prior to
work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable
hazards or ignition risks. “No Smoking” signs shall be displayed.
7. Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or
conducting any hot work. A degree of ventilation shall continue during the period that the work is carried
out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the
atmosphere.
8. Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and to the correct
specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt
consult the manufacturer’s technical department for assistance.
The following checks shall be applied to installations using flammable refrigerants:
- The charge size is in accordance with the room size within which the refrigerant containing parts are installed;
- The ventilation machinery and outlets are operating adequately and are not obstructed;
- If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of
refrigerant;
- Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be
corrected;
- Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any
substance which may corrode refrigerant containing components, unless the components are constructed of
materials which are inherently resistant to being corroded or are suitably protected against being so corroded.
9. Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and component inspection
procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to
the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to
continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the
equipment so all parties are advised.
Initial safety checks shall include:
-That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;
-That there no live electrical components and wiring are exposed while charging, recovering or purging the
system;
-That there is continuity of earth bonding.
17.
Repairs to sealed components
1. During repairs to sealed components, all electrical supplies shall be disconnected from the equipment
being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical
Summary of Contents for TT26X71-0932IA
Page 33: ...33 BG 4A 250V III 50 cm 8...
Page 34: ...34 BG...
Page 35: ...35 BG No 1 2 3 4 LED 5 6 7 8 9 10 11 12 No 13 14 15 16 17...
Page 36: ...36 BG No Led 1 SLEEP SLEEP 2 1 Timer 2 3 TIMER Timer COOL 3 HEAT 5 COOL...
Page 40: ...40 BG 1 2 3 4 1m flashing swing 1 1 2 deactivate 2 2 2 1 2 deactivate flashing 3 2 2 Fan...
Page 47: ...47 BG 10Pa 5g 10g A 5 B 10 C D A B 22 R290 R161 R410A 32 Water drain pipe...
Page 48: ...48 BG mm 250cm...
Page 49: ...49 BG 1 65 2 1 2 3 4 PCB 1 2 32mm 3 4 5...
Page 50: ...50 BG 3 1 3 1 2 3 4 R32 R290 1 2 3 4 1 2...
Page 51: ...51 BG 1 2 3 4 1 25mm 2 1 2 3 4 5 6 1...
Page 53: ...53 BG 1 2 3 4 ON OFF FAN MODE TIMER 6 1 4 7 7 1 2 8 1 8 8 t...
Page 57: ...57 BG 6 N B LCD 1 2 3 45 C 4 5 1 2 40 3 1 2 3...
Page 58: ...58 BG TIMER ON LIGHT...
Page 59: ...59 BG IPM PCB EEPROM 1 2 4m2 3 4 4m2 5 6 7 8 9 10 11 12 13 14 15...
Page 60: ...60 BG 16 1 2 3 4 5 CO2 6 7 8 9 17 1...
Page 61: ...61 BG 2 18 19 20 21 LFL 25 OFN 22 OFN OFN OFN...
Page 62: ...62 BG 23 a b c d e f g h 80 i j k 24 25...
Page 64: ...64 24 13 12 TESLA 1 2 2 1 2 2 TESLA 2 3 2 4 2 5 2 6 2 7 2 8 2 9 2 10 2 11...
Page 65: ...65 2 12 3 4 5 6 7 8 112 115 119 112 1 2 1 2 3 113 1 2 3 2 114 4 5 114 1 113 1 2 2 3...
Page 66: ...66 115 4 115 1 2 1 3 1 1 10 02 9700970 02 9700971 9 30 19 00 10 00 16 00...
Page 67: ...67...
Page 68: ...68 GR 4A 250V H 50 cm 8...
Page 69: ...69 GR...
Page 70: ...70 GR 1 2 3 4 LED 5 6 7 8 9 10 11 12 13 14 15 16 17...
Page 71: ...71 GR 1 SLEEP 2 1 2 3 3 5...
Page 73: ...73 GR HEALTH 3 Ap 1 2 3 4 AUTO 5 COOL 6 DRY 7 FAN 8 HEAT 9 ECO ECO...
Page 75: ...75 GR 1 2 3 4 1 m 1 1 2 2 2 2 t 1 2 2 2...
Page 76: ...76 GR FAN MODE COOL 1 2 3 MODE HEAT 1 2 3 MODE DRY MODE FAN MODE AUTO 2 10...
Page 82: ...82 GR 10 Pa 5 g 10 g A 5 B o 10 A B R22 R290 R161 R410A R32...
Page 83: ...83 GR mm 250 cm...
Page 84: ...84 GR 1 65 2 1 2 3 4 1 2 32 mm 3 4 5...
Page 85: ...85 GR 3 1 3 1 2 3 4 R32 R290 1 2 3 4 1 2 NAI OXI NAI OXI OXI...
Page 86: ...86 GR 1 2 3 4 1 25 mm 2 1 2 3 4 5 6 1 1...
Page 88: ...88 GR 1 2 3 4 MODE 3 2 3 6 1 4 7 7 1 2 8 1 8 8...
Page 92: ...92 GR 6 LCD 1 2 3 45 oC 4 5 1 2 40 C 3 1 2 3...
Page 93: ...93 GR...
Page 94: ...94 GR IPM EEPROM 1 2 4 m2 3 4 4 m2 5 6 7 8 9 10 11 12 13 14 15...
Page 95: ...95 GR 16 1 2 3 4 5 CO2 6 7 8 9...
Page 96: ...96 GR 17 1 2 18 19 20 21 LFL 25 OFN 22 OFN...
Page 97: ...97 GR OFN OFN 23 80 24 25...
Page 99: ...99 TESLA 8 9 TESLA email warranty gr comtrade com...
Page 100: ...100 1 Service 2 Service 3 Service 4 Service 5 Service 6 Service 7 Service 8 Service 9 Service...
Page 270: ...www tesla info...