25
SIA user account ID
: in case of using the SIA IP protocol, the supervision messages are sent to
CMS using the user account ID configured in this section. The length of the SIA user account ID
is 1 to 6 hexadecimal characters, and the following characters can be used: 0..9, A, B, C, D, E,
F. Do not fill in the account ID section with zeros!
Note!
The user account ID, group ID, device ID and SIA user account ID are only needed if
reporting to CMS is used.
Low supply voltage event
:
Low voltage threshold
:
the device has built-in supply voltage monitoring function. In this
section you can configure the threshold from 10 to 30V, at which the device will generate
the “
Low supply voltage
” event. The event will be generated if the supply voltage is
continuously at, or below the configured level for at least 30 seconds
.
Low voltage restore threshold
:
In this section you can configure the threshold from 10 to
30V, at which the device will generate the “
Low supply voltage
” restore event. The event
will be generated if the supply voltage is continuously at, or above the set level for at
least 30 seconds after a “
Low supply voltage
” event
.
System time
:
NTP server 1,2
: in this section you can select one of the default NTP servers or you can also
configure custom NTP servers which you wish to use for system time synchronization.
The device synchronizes the system time from the GSM network and if this fails, it will use the
NTP servers. If synchronization from the NTP servers also fails, it will synchronize the date and
time using the timestamp received from a CMS server/receiver, if CMS is used.
Time zone
: select the time zone according to the location of installation. The device adjusts the
system time according to the time zone setting. If the setting is wrong, there will be difference
between the system time and the local time and therefore the timestamps of the events will also
be wrong and the periodic test report will also be sent at the wrong time of day.
Miscellaneous settings:
Incoming call from unknown phone number
: in this section you can configure what the
device should do upon a phone call received from a phone number which is not configured in the
device as a user phone number, or a call received with hidden caller ID. You can configure the
device to accept or reject these calls. Independently of the selected option, receiving a call from
an unknown phone number also generates a service event, which you can configure separately
to control the output(s) or send notifications.
SMS forwarding phone number
: the device forwards the messages received by its SIM card to
the phone number configured in this section (e.g. balance information received from the GSM
service provider in case of pre-pay card). The received messages are deleted automatically after
forwarding. If no phone number is configured, the device deletes all incoming messages without
forwarding.