Note: In order to clear the faults listed above, the RSSI button must be
pressed twice. After the issue has been resolved and the unit cleared,
STEPS 3 AND 4 MUST BE REPEATED OR THE TELGUARD UNIT
WILL NOT TRANSMIT ANY SIGNALS.
Illuminated LEDs
Indication
LED 1 & 4 flashing
Failed Activation – Call Technical Support
All LEDs flashing
Activation Error – Signal Too Weak
LED 1 On
Activation Successful
System Status LEDs Table
Status LED #2
Indication
1 FLASH
STC – Low Power Failure
2 FLASH
N/A
3 FLASH
N/A
4 FLASH
NSC – No Service
5 FLASH
RFC – Radio Failure
6 FLASH
DTF – Dial Tone Failure
7 FLASH
PPF – Panel Presence Failure
System Trouble Condition, STC (LED #2) Table
If no LEDs besides the STC LED are lit or flashing, it may indicate
insufficient power supplied from the alarm panel. Press and release
the RSSI button to change the LEDs to RSSI mode. If still no LEDs
are lit, then check the voltage being supplied to the Telguard unit
and ensure that it is above 6V.
Connect Alarm Panel to Telguard Unit
If the alarm panel and the Telguard TG-1 Express were not already connected
in Step 2, plug the modular jack of the alarm panel to the RJ-45 jack on the
Telguard unit.
Verify Alarm Signal Transmissions over Cellular
Trip several alarms on the alarm panel and verify that the central station
received them by calling the central station operator. Use a lineman's butt-set
in
MONITOR MODE
and connected to Telguard unit’s "T" and "R" test pins