ADR-7000 / SAVER-7000 / GUARD-7
© 2017
– Telefire Fire & Gas Detectors Ltd
Revision 0.98 October 2017
– Page 52 of 87 –
Screen 36 Walk test
– main screen
8.6.2 View Progress
Selection option
2 View Progress
shall show the total number of devices tested.
Screen 37 Walk test
– progress report
8.6.3 Config Parameters
This menu allows setting the time until automatic reset during walk test (options are one
second to 30 seconds in 1 second steps. Default: 10 seconds).
It is also possible to set the exit from test mode to be either manual (default) or
automatic (5 to 60 minutes, default: 15 minutes).
Screen 38 Walk test parameter
IS 1220
IS 1220 Requirement
IS 1220 requires that exit from Walk Test shall be automatic and within 30
minutes. Ensure you change this setting to comply with IS 1220.
UL
UL Requirement
UL 864 requires that exit from Walk Test shall be automatic and within 30
minutes. Ensure you change this setting to comply with UL 864.