ADR-7000 / SAVER-7000 / GUARD-7
© 2017
– Telefire Fire & Gas Detectors Ltd
Revision 0.98 October 2017
– Page 27 of 87 –
!
Warning
Do not connect extinguishing devices at this time. Use a dummy load
to test.
4.4.5 Connecting AC Power
Connect the control panel’s AC input line to a dedicated circuit breaker that is not shared
by other appliances or equipment. It is recommended that the circuit breaker shall be
clearly labeled "FIRE ALARM".
The power cable should enter the control panel through either the top left or bottom left
knockout opening and separated from the field wiring Use a plastic bushing that fits the
opening. Connect the Live and Neutral wires to the proper terminal. Connect the
Ground wire directly the panel's chassis using the marked ground screw.
4.4.6 Site-Specific Configuration (Programming)
Control panel programming shall include the control panel's configuration; device
properties and description; and activation matrices.
It can be done in one of two ways:
Pre-planning by using the TCS-7030 software and creating a configuration plan and
downloading it to the control panel. Compare planned and installed configuration
after download.
Perform auto-program by using
Error! Reference source not found.
(see section
Error! Reference source not found.
on page
Error! Bookmark not defined.
).
The control panel shall scan every address on every loop. Every device that is
physically connected to the control panel shall automatically be enabled, and
configured as the default options for that particular device type. It is possible to
modify parameters and options from the control panel or tcs730.
See chapter
Error! Reference source not found.
on page
Error! Bookmark not
defined.
for a detailed description.
4.4.7 Ensure All Devices are identified
Compare the number of devices scanned by the control panel to planned devices to
check for misconfigured or uninstalled devices.
4.4.8 Initialize Detectors
Each smoke detector adjusts itself gradually according to changes of environmental
conditions, by measuring and calculating the new reference value needed for signal
processing.
This process normally requires a period of several hours. When the system is turned on
for the first time, or after installing or changing a detector, it is recommended to perform
the initialization process.
If this action is not performed, the adjustment will be completed automatically within a
few days of operation.
See section
Error! Reference source not found.
on page
Error! Bookmark not
defined.
for an explanation on performing detector initialization.
i
Note
Ensure that detector initialization is performed when all detectors are in a
smoke-free condition.