For switches: Alarm; Reset; Silence; Disconnect; Supervisory; Abort; Release;
Alarm Matrix; or Fan PC
For sounder / strobe: whether this NAC works as the protocol that is defined in
the control panel or without protocol.
For extinguishers: the extinguishing pulse length
N/A for all other devices
Delay
: alarm verification time for detectors, or an output activation delay. Can be
between 0 and 50 seconds.
Silenced
: whether this output is silenced
0
: not silenced
1
: silenced; re-activated by any alarm
2
: silenced; re-activated only by devices in this output's matrix
Event Control
: activation conditions:
General
: activated by any alarm
Device Matrix
: a group of input devices should be selected to form a matrix in
order to activate the configured output device. The number of devices in alarm
required to activate the output device must be set between 1 (default) and 6.
Zone Matrix
: A Zone Matrix is an activation array of one or several logical
device zones that are assigned to an output device in order to form complex
activation functions.
Alarms from all selected zones
: number of alarms from any device in any
of the selected zones (i.e., 2 selected alarms from zones 1, 2, and 3 would
be activated by any 2 alarms from any 2 devices in zones 1, 2, and 3).
Alarms in a selected zone
: number of alarms from any device in one of
the selected zones (i.e., both alarms need to be in the same zone).
Zones in alarm
: number of zones out of the selected sets that need to be
in alarm (i.e., "2 zones in alarm" from zones 1, 2, and 3) requires that at
least one device in each of two separate zones be in alarm.
i
Note
An input module or switch that are configured as
Alarm Matrix
will activate a
matrix output even if it requires two or more alarms to activate.
8.10.2 Automatic Device Programming
Automatic device programming causes the control panel to scan every possible address
and populate its device map according to whatever devices are installed.
Every connected device shall be configured as “Active” and with the correct device type
and the default configuration of that device type.
Setting logical zones, activation matrices, and other parameters requires operator
intervention (manual programming).
This will allow comparing the system as installed to planned configuration in order to find
any installation-related problems.