ADR-7000 / SAVER-7000 / GUARD-7
© 2017
– Telefire Fire & Gas Detectors Ltd
Revision 0.98 October 2017
– Page 5 of 87 –
Line Cards
Max. Addresses
Line Cards
Max. Addresses
4
508
8
1,016
Table 1
Maximum addresses by configuration
– ADR-7000
2.2.2 Maximum Addresses
– SAVER-7000
All loop cards are capable of communicating with up to 127 addresses, and the
maximum number of addresses is a 254.
Line Cards
Max. Addresses
1
127
2
254
Table 2
Maximum addresses by configuration
– SAVER-7000
2.2.3 Maximum Addresses
– GUARD-7
The GUARD-7 has 60 addresses.
2.3
Keyboard and Display Module
– ADR-7003
The keyboard and display module contains a graphic LCD display (240 x 64 pixels),
indicating LED display, and keys for programming and operation. The display and
keypad meet the strict standards of UL 864, EN 54, and IS 1220.
The display and keypad have six main areas:
Graphic LCD display
General display area
Fault display area
Additional indication area
Keyboard
Zone indication LEDs
See detailed explanations on page 22.
2.4
Power Supply
The ADR-7000 has a 150W power supply that accepts 110-240Vac (nominal) input.
2.5
Zone Alarm Module
– ADR-7000ZM
The optional Zone Alarm Module may be installed in the ADR-7000 to visually indicate
zones in alarm.
2.6
Network Communication Module
– LON-7000
The LON-7000 is a communication module that enables connection between control
panels to establish a network. A two-wire copper cable connection is required to
interconnect between the control panels. Optionally fiber-optic connection is made
possible with additional modules. The length of the wires depends on the connection
topology and media type (copper or fiber optic). Please refer to the LON-7000 technical
manual for further details.