MULTIFLAME DF-TV7
OPTICAL FLAME DETECTOR
OPERATING MANUAL
NOSP17662
Revision 03
23
Relay card, terminal block (option):
Point
JP2
Description
1
C1
Relay1 common
2
R1
Relay 1 de-energized
3
T1
Relay 1 energized
4
T1
Relay 1 energized
5
C2
Relay 2 common
6
C2
Relay 2 common
7
R2
Relay 2 de-energized
8
T2
Relay 2 energized
9
T2
Relay 2 energized
10
C3
Relay 3 common
11
R3
Relay 3 de-energized
12
T3
Relay 3 energized
4.3.5
EOL Resistor
This applies to ATEX/IEC installations only. The EOL resistor must only be used
inside the housing on the terminal block.
This configuration allows the detector to be connected to PLC.
Because this type of device cannot operate the detector’s 4-20 mA signal, the relays are used to
interface with the detection loop.
Connecteur alimentation / signal
Connecteur relais : 2 connecteurs avec détrompeur
Summary of Contents for Everywhereyoulook MultiFlame DF-TV7
Page 20: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 14 NOSP17662 Revision 03...
Page 34: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 28 NOSP17662 Revision 03...
Page 56: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 50 NOSP17662 Revision 03...
Page 60: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 54 NOSP17662 Revision 03...
Page 61: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL NOSP17662 Revision 03 55...
Page 62: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 56 NOSP17662 Revision 03...
Page 63: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL NOSP17662 Revision 03 57...