In this case, the output current is not isolated from power supply, consumed by the detector.
The 20mA current loop must be supplied with a PLC. The current return must be connected to the
0V at the level of the L- terminal. To proceed, please connect the 4 (V-) and 6 (L-) terminals at the
terminal block level of the device.
4.3.3.3
4-wires connection (isolated power)
When using a 4 wires connection, the current loop is provided by the input module or PLC. The
loop (L + and L-) is optically isolated from the detector. 4-20mA or 0-22mA input module of the
PLC has to power up the current loop with, at least 8V at the terminal level.
4.3.4
Relay
An optional card with 3 relays can be added on the detector.
The output relays can be connected to the detection unit or warning devices.
For the network version, the optional relay card cannot be installed.
Each relay can be configured:
•
normally closed or normally open.
•
on one or more states of the detector (fault, permanent Inhibition, alarms).
For relays configuration and factory settings, refer to §6.8.3.3
Summary of Contents for Everywhereyoulook MultiFlame DF-TV7
Page 20: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 14 NOSP17662 Revision 03...
Page 34: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 28 NOSP17662 Revision 03...
Page 56: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 50 NOSP17662 Revision 03...
Page 60: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 54 NOSP17662 Revision 03...
Page 61: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL NOSP17662 Revision 03 55...
Page 62: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 56 NOSP17662 Revision 03...
Page 63: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL NOSP17662 Revision 03 57...