MULTIFLAME DF-TV7
OPTICAL FLAME DETECTOR
OPERATING MANUAL
NOSP17662
Revision 03
33
6.4
Power and fault indications
A green LED located in the communication head blinks
at 0.5 Hz in normal operation mode.
When the device communicates with the TLU, the
frequency goes to 1Hz. When the magnetic wand is
applied on the detector, the LED remains steady.
In Fault mode, the LED frequency goes down to 0.3Hz.
6.5
Alarm indication (LED)
A red LED placed in the communication head blinks
when in fire alarm.
In standard configuration, the fire alarm is latched and
the red LED keeps blinking until it is acknowledged with
the TLU or the magnetic wand or until the detector is
powered cycle.
With respect to
DF-TV7-X##0-0X#-0N
versions, the
fire alarm is unlatched and the LED stops blinking when
the fire alarm disappears.
DF-TV7-X##0-0X#-0N versions are not EN 54-10 compliant.
When the fire alarm is latched, the red LED keeps blinking until the alarm is reset.
Summary of Contents for Everywhereyoulook MultiFlame DF-TV7
Page 20: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 14 NOSP17662 Revision 03...
Page 34: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 28 NOSP17662 Revision 03...
Page 56: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 50 NOSP17662 Revision 03...
Page 60: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 54 NOSP17662 Revision 03...
Page 61: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL NOSP17662 Revision 03 55...
Page 62: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 56 NOSP17662 Revision 03...
Page 63: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL NOSP17662 Revision 03 57...