Installation
The detector must be installed in accordance with its certification and with the
standards of the appropriate authority in the country concerned.
4.1
Location
The detector should be positioned above the targeted danger zone and at a distance
corresponding to the type of fire it has to detect.
Be aware of potential radiation sources as these may trigger a false alarm. If possible, install the
detector in clean zone, sheltered from major vibrations. For maximum effectiveness, avoid
exposing the head of sensor to alternation of light and shade (passing vehicles, tree branches…).
IR sources (particularly if modulated) like hot machinery, exhaust outlets, etc. may also de-
sensitize the detector, masking the radiation from a small fire.
For detectors using the UV wavelength:
Do not position the detector behind a glass window as this blocks UV radiation.
Locations where smoke, gas or vapours capable of absorbing UV radiation could
accumulate (e.g. ceilings) should be avoided as well.
Detector fields of vision may be overlapped, particularly if the devices are used in a voting
configuration.
The detector should have a direct line-of-sight to the potential fire source. Partial obstruction may
reduce detection rate.
For an inclination of 10°, there is
a semicircle blind zone, directly
below the detector, with a radius
of 0.8 times the detector height.
With this angle, the optical axis
“touch” the ground at a distance
of 5.7 times the height.
Summary of Contents for Everywhereyoulook MultiFlame DF-TV7
Page 20: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 14 NOSP17662 Revision 03...
Page 34: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 28 NOSP17662 Revision 03...
Page 56: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 50 NOSP17662 Revision 03...
Page 60: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 54 NOSP17662 Revision 03...
Page 61: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL NOSP17662 Revision 03 55...
Page 62: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 56 NOSP17662 Revision 03...
Page 63: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL NOSP17662 Revision 03 57...