MULTIFLAME DF-TV7
OPTICAL FLAME DETECTOR
OPERATING MANUAL
NOSP17662
Revision 03
31
6
Operation
6.1
Environmental conditions
•
Dust: Dust on the window may limit UV sensitivity
•
Oil vapour: Oil vapour on the window can reduce UV sensitivity
•
Water/Ice: The presence of Water or ice can reduce flame detector performances at an
infrared level.
6.2
Inhibition
Maintenance Inhibition is temporary. It appears during power up and maintenance phases.
Inhibition stops automatically when the operator leaves the maintenance menus or 10 minutes
after the end of communication with the TLU.
Maintenance inhibition can be configured in "frozen" mode (factory setting) or in "free" mode by
the TLU or via the HART protocol. It cannot be configured by the magnetic wand.
•
In "frozen" mode, outputs (current and relay) remain in their previous state.
•
For example, if the device indicated a failure (2.0 mA), this state would be maintained
during the inhibition.
•
If the unit is configured in "free" inhibition mode, the output current will be on the same
level as for the permanent inhibition
The permanent inhibition is activated by an order issued by the TLU when an operation is
performed at/or around the device, or when the operator wants to inhibit a faulty device. The
permanent inhibition must be removed by an operator’s deliberate action using the TLU.
When working with the LT15 test lamp, the detector must be in TEST-mode. The default output is
in maintenance inhibition; but the detector’s outputs (current loop and relays) may be activated
in order to test the complete loop (Requires access level 2 on the TLU).
Local LED and Information on the TLU are activated anyway.
Summary of Contents for Everywhereyoulook MultiFlame DF-TV7
Page 20: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 14 NOSP17662 Revision 03...
Page 34: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 28 NOSP17662 Revision 03...
Page 56: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 50 NOSP17662 Revision 03...
Page 60: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 54 NOSP17662 Revision 03...
Page 61: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL NOSP17662 Revision 03 55...
Page 62: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 56 NOSP17662 Revision 03...
Page 63: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL NOSP17662 Revision 03 57...