CAUTION!
Do not put the process connection near to the product inlet. If the product that enters the tank
touches the probe, the device will measure incorrectly.
Figure 3-7: Do not put the device near to a product inlet
1
The device is in the correct position.
2
The device is too near to the product inlet.
3
If it is not possible to put the device in the recommended position, install a deflector pipe.
Figure 3-8: How to prevent build-up of product around the process connection
1
If product particles are likely to collect in holes, a nozzle is not recommended.
2
Attach the flange directly to the tank.
3
Use a threaded connection to attach the device directly to the tank.