Cable gland
Standard: none
Input and output
Current output
Current output
Current output
Current output
Output signal
(Output 1)
4
…
20 mA HART
®
or 3.8
…
20.5 mA acc. to NAMUR NE 43
6
Output signal
(Output 2
–
optional)
4
…
20 mA (no HART
®
signal) or 3.8
…
20.5 mA acc. to NAMUR NE 43 (optional)
Resolution
±
3
µ
A
Temperature drift
Typically 50 ppm/K
Error signal
High: 22 mA; Low: 3.6 mA acc. to NAMUR NE 43
Approvals and certification
CE
This device fulfils the statutory requirements of the EC directives. The
manufacturer certifies successful testing of the product by applying the CE mark.
Explosion protection
Explosion protection
Explosion protection
Explosion protection
ATEX
KEMA 04ATEX1218 X
II 1 G, 1/2 G, 2 G Ex ia IIC T6...T2 Ga or Ex ia IIC T6...T2 Ga/Gb or Ex ia IIC T6....T2 Gb;
II 1 D, 1/2 D, 2 D Ex ia IIIC T95°C Da or Ex ia IIIC T95°C Da/Db or Ex ia IIIC T95°C Db;
II 1/2 G, 2 G Ex ia/d IIC T6..T2 Ga/Gb or Ex d ia IIC T6...T2 Gb;
II 1/2 D, 2 D Ex ia tb IIIC T95°C Da/Db or Ex ia tb IIIC T95°C Db;
II 3 G Ex nA II T6
…
T2 X
FM
–
Dual Seal-approved
NEC 500
NEC 500
NEC 500
NEC 500
XP-IS / Cl. I / Div. 1 / Gr. ABCD / T6-T1;
DIP / Cl. II, III / Div. 1 / Gr. EFG / T6-T1;
IS / Cl. I, II, III / Div. 1 / Gr. ABCDEFG / T6-T1;
NI / Cl. I / Div. 2 / Gr. ABCD / T6-T1
NEC 505
NEC 505
NEC 505
NEC 505
Cl. I / Zone 0 / AEx d[ia] / IIC / T6-T1;
Cl. I / Zone 0 / AEx ia / IIC / T6-T1;
Cl. I / Zone 2 / AEx nA[ia] / IIC / T6-T1
Hazardous (Classified) Locations, indoor/outdoor Type 4X and 6P, IP66, Dual Seal
Technology Solutions
Instruction Manual
Tek-Flex
4100A
www.tek-trol.com
1
21