You can change the reference point from which level is measured. Use the menu item "Tank
Bottom Offset" (C.1.11). If you move the reference point below the tank bottom, add this value
when give a level for the 4 and 20 mA current output settings. If you move the reference point
above the tank bottom, subtract this value when you give a level value for the 4 and 20 mA
current output settings.
For more data about the menu items, refer to
Function description
on page 73 (table C. Advanced
setup).
6.4.6 How to configure the device to measure volume or mass
The device can be configured to measure volume or mass. You can set up a strapping table in the
conversion table in the device's Quick Setup
Quick Setup
Quick Setup
Quick Setup menu.
How to create a volume or mass table.
•
Go to Supervisor > Quick setup > Setup mode > Conversion
Supervisor > Quick setup > Setup mode > Conversion
Supervisor > Quick setup > Setup mode > Conversion
Supervisor > Quick setup > Setup mode > Conversion.
•
Complete all the steps in the set-up procedure.
The device creates a table of up to 50 pairs of data (level
–
volume or level
–
mass). The
reference point for the table is the tank bottom (as given in menu item C.1.2 Tank Height).
Figure 6-5: Level measurement
1
Tank Bottom Offset (C.1.11)
2
Tank Height (C.1.2)
3
Blocking Distance (C.1.9)
4
Maximum effective measuring range
5
20 mA Setting (C.3.3 or C.4.3)
6
4 mA Setting (C.3.2 or C.4.2)
7
Non-measurement zone
INFORMATION!
You can also create customized length and conversion units (free units) in the Conversion
Conversion
Conversion
Conversion setup
procedure.