MA7200 PLUS Operating Manual
TECO – Westinghouse Motor Company (Sn-30–Sn-32) Multi-Function Output
Cont.
Parameter Details
Sn-30-32=00
During Running
OFF Run source OFF, inverter is off.
ON
Run source ON, or Run source OFF but some residual output
exists
Sn-30-32=01
Zero Speed
OFF Output frequency
≥
MIN. output frequency (Cn-07)
ON Output frequency
<
MIN. output frequency (Cn-07)
Sn-30-32=02
Frequency Agree
Sn-30-32=03
Setting Frequency Agree
Sn-30-32=04
Output Frequency Detected 1
Sn-30-32=05
Output Frequency Detected 2
Refer to frequency detection function on page 3-21.
Sn-30-32=06
Inverter Ready
Sn-30-32=07
Undervoltage Detected
When the DC link voltage of main circuit is lower than the UNDERVOLTAGE DETECTION LEVEL set
by parameter Cn-39, the output contact is in the ‘ON’ state.
Sn-30-32=08
Output Blocked
Sn-30-32=09
Run Command Mode
OFF
Remote Mode:
When parameter Sn-04=1or 2, or one of multi-function input terminals
-
is set as
Local/remote control I mode or Local/remote control II mode and the input to the terminal is
OFF. The Remote SEQ LED on digital operator is ON.
ON
Local Mode:
When parameter Sn-04 = 0 or the multi-function input terminal
-
is set as Local/remote
control I mode and contact terminal is ON. The Remote-SEQ LCD is OFF, and the RUN
command is from the digital operator.
Sn-30-32=10
Frequency Command Mode
OFF
Remote mode:
When parameter Sn-05 = 1,2 or one of the multi- function input terminals
-
is set as
Local/remote control I mode or Local/remote control II mode and the input to the terminal is
OFF. The Remote-REF LED on the digital operator is ON.
ON
Local mode:
When Sn-05 = 0 or one of the multi- function input terminasl
-
is set as Local/remote
control I mode and contact terminal is ON. The Remote-REF LED is OFF and the RUN
command is from digital operator.
Sn-30-32=11
Excess Load Detection (N.O. Contact)
See page 3-22, 3-44 for excess load detection function.
Sn-30-32=12
Frequency Command Missing
When the Run source is ON and the frequency command is 0, the output at the multi-function output
terminal is ON.
Cont.