MA7200 PLUS Operating Manual
TECO – Westinghouse Motor Company P1-03 - P2-04
cont.
– P1-07 Parameter Details
Sn-69
Torque Detection 2 Selection
The parameter is not available for software version 77.01 and later.
Use parameter Sn-12 for excess load detection and parameter P3-03 for load loss detection as an alternative.
Sn-70
Engineering Unit
The parameter is not available for software version 77.01 and later.
Use parameter P1-01 for engineering unit as an alternative.
9.2.4 Parameters P
П
(Application Parameters)
The P parameters, together with interacting parameters from other groups, are used to set and control the following
eleven categories In this section only the P parameters are described in detail. The other related parameters are
described in their own individual sections
1. Scaled Feedback and Engineering units
2. Programmable Local / Remote Switch
3. PID Sleep Functions
4. External PID Functions (Input / Output Terminal)
5. External PID Functions (Gain Setting and Monitoring)
6. Load Loss Detection Function
7. Over Feedback Function for PID Feedback Signal
8. Low Feedback Function for PID Feedback Signal
9. Low Suction Detection Function
10. Flow Meter Display
11. Power Meter, KWh Meter, and Energy Cost Usage.
P1-01
Engineering Unit (00-25)
P1-01Engineering Unit is used to setup engineering units for normal and PID operation. It also sets the display
format and maximum value of the following parameters.
1 - Set point frequency command (An)
2 - The parameters for the engineering units.
3 - PID feedback monitor point Un-34.
When
P1-01 is set to 00, parameter Cn-28 can be used to set the display format of the frequency commands.
When P1-01 is set to a value of 01 to 25, parameter Cn-28 is ineffective.
The following Table 9.2.4.1 shows the display format and maximum value according to the setting of P1-01.
Table 9.2.4.1
Setting
of
P1-01
Display Format
Maximum Value
Set Point and
Freq. Command
PID Feedback
Monitor and
Engineering
parameters
Set Point and
Freq. Command
PID Feedback
Monitor and
Engineering
parameters
0
Follow the
Setting of Cn-28
XXX.XX %
Follow the
Setting of Cn-28
100.00%
1 XXX.XX
%
100.00%
2 - 25
XXXX
Parameter P1-02