MA7200 PLUS Operating Manual
TECO – Westinghouse Motor Company App-2 Fan and Pump
key
Keypad Steps
Resulting Display
1 - Press the
2 - Press the
3 - Press the
key and the the
key 3 times and then the
Finally set parameter
P2-04 = 5.0 sec
(Sleep Wakeup Delay)
EDIT
ENTER
key to
save
.
4 - Press the
Entry Accepted
2 Seconds
DSPL
EDIT
ENTER
Flashing
RESET
Flashing
key
key 5 times
Flashing
P2-04-
Sleep Wakeup Delay
P2-04=000.
0
s
Sleep Wakeup Delay
P2-04=00
5
.0 s
Sleep Wakeup Delay
PRGM
DRIVE
key to return to the main display.
5 - Press the
P2-04=00
5
.0 s
Sleep Wakeup Delay
Step 7
– Testing The System
The system can now be tested for performance. To do this, set the
set-point
through the keypad and run the drive
at some low level and check that the motor is operating properly and that the
feedback
signal level and polarity are
correct.
Check the system for dynamic operation and make any adjustments necessary for optimum performance. This may
require making adjustments to parameters
Bn-17 proportional gain
and
Bn-18 Integral Time. (Refer to Step 4)
NOTE: Parameters Bn-17 and Bn-18 may be changed through the keypad while the
system is operating.
A word of CAUTION ! - The parameter changes should be made in small increments and the results
checked to avoid highly unstable and possibly damaging conditions.
This should complete the example installation of a system with a PID loop.