MA7200 PLUS Operating Manual
TECO – Westinghouse Motor Company App-2 Fan and Pump
To further cover the PID Sleep function, the following is an example of the various parameter settings that could be
used. In this example the system will have the following specifications:
-
Max. Pump Motor Speed: 3600 RPM.
-
Set Point: 150 PSI.
-
Feedback Transducer Range: 0 – 200 PSI.
-
Pump System Sleep Level: 2160RPM or
60%
of max. speed set by
(P2-01=060.00).
Sleep Level Delay Time: 10 sec. set by
(P2-02=010.0 ).
-
Pump System Wakeup Level: 100 PSI
set by
(P2-03=0100).
Wakeup Time: 5 sec. set by
(P2-04=005.0).
Referring to
Step 3,
set the engineering units to
PSI
(
P1-01=02)
and then the range to 200
(P1-02=0200).
The following shows the keypad navigation sequence in setting the PID parameters.
NOTE: The inverter must be in the Stop mode in order to turn on the sleep function.
PRGM
DRIVE
DSPL
Key 4 times
Keypad Steps
Resulting Display
1 - Press the
2 - Press the
3 - Press the
key
An – 01 -
Freq. Cmd. 1
key 3 times
Set parameter
P1-04 = 1
(Turn on Sleep function)
Flashing
4 - Press the
key
5 - Press the
P1-01-
Engineering Units
PID Sleep Function
P1-04 -
EDIT
ENTER
P1-04 =
0
PID Sleep Invalid
key
P1-04 =
1
PID Sleep Valid
Flashing
EDIT
ENTER
key to
save
6 - Press the
Entry Accepted
2 Seconds
P1-04 =
1
PID Sleep Valid
Flashing
Go to next step
Cont.