MA7200 PLUS Operating Manual
TECO – Westinghouse Motor Company Control Terminals Functions
Fig. 4.2.4 PG Interface Wiring
Notes:
1 - Use twisted pair shielded cable and connect the shields to ground as shown.
2 - Terminal description:
Terminal
Description
A(+)
PG signal input terminal.
Voltage level (H: 4 -12V, L:
1V).
Max. frequency is < 32767 Hz
A(-)
IP12
External power source input (+12V
10%@ 40mA max.)
IG12
+12V
External Power source (+12V
10%, @ 0.5A min.)
0V
E Inverter
ground.
3 - The A(+), A(-), IP12 and IG12 terminals are integrated in connector CN2 in compact version. (See Fig. 2.1.1).
The code No. for the wiring is 4H339D0250001.
4 - The PG interface only supports an open-collector or complementary interface.
5 - The jumper TP1 is set to the PULL UP position for an open-collector interface (factory setting) and to the
OPEN position for a complementary interface.
6 - The shielded twisted-pair cable used between the inverter and the PG should be less than 150 feet in length.
7 - Refer to the parameters in Section 9.0 for the settings used in the PG set-up.
Cont.