MA7200 PLUS Operating Manual
TECO – Westinghouse Motor Company Sn-29
Cont
. Parameter Details
Table 9.2.3.5 Multi-function Analog Input Functions
(Cont.)
Setting
Function
LCD Display
Description (100% output corresponds to 10 V level)
07
DC injection braking
DC Brakin current
According to analog input voltage (0-10V), change the
level of DC injection current (0-100
%
).
(inverter rated current=100%, the setting of DC injection
current Cn-15 is disabled )
08
Stall prevention level
during running
Run Still Level
According to analog input voltage (1.5V-10V), change the
level of stall prevention during running (30%-200%)
(inverter rated current=100%, the setting Cn-26 is
disabled.)
09
PID control reference
input
PID Command
Multi-function analog input (terminal AUX) used as PID
control reference input (0-10V). Refer to App-1 PID
Application Note.
10
Frequency command
lower limit
Freq. Cmd. Low
Bound
Changes the frequency command lower-limit (0-100
%
)
value according to the then analog input voltage (0-10V)
(Max. output frequency (Cn-02) corresponds to the 100%
analog output. The actual lower-limit is determined by the
maximum value of Cn-19 and the value corresponding to
the multi-function analog input terminal).
11
Jump frequency setting4
Freq Jump 4
Sets the jump frequency 4, according to analog input
voltage (0-10V), while Cn-20 to Cn-23 can be used to set
the jump frequency 1-3 and their jump frequency width.
12
RS-485 communication
application
Comm. Control
The analog value of AUX 0 – 10V can be read through
serial communication (RS485). The scaling is
(0 -10V = 0 – 1024)
13
Frequency instruction
gain 2 (FGAIN)
Instruction gain2
With Bn-05, 06 (or Bn-07, 08) set, adjust analog
frequency instruction gain and bias ( gain and bias
adjustment is similar to 7200GA)
14
Frequency instruction
bias 3 (FBIAS1)
Instruction bias 3
?
15
Frequency instruction
bias 4 (FBIAS2)
Instruction bias 4
?
16
Load Loss Level
Load Loss Level ?
17
Flow Meter
Flow Meter
?
18
External PID Set Point
Ext. PID Set Point ?
19
External PID Feedback
Ext. PID Feedback ?
The AUX analog input can provide two groups of gain and bias; Sn-29 =1-3 and Sn-29=13-15. When
Sn-29=13-15, the adjustment of gain and bias is similar to the GA series. (See Fig. 9.2.3.17)
Fig. 9.2.3.17 Gain and Bias
The following Fig. 9.2.3.18 shows the multi – function analog input characteristics.
Cont.