MA7200 PLUS Operating Manual
TECO – Westinghouse Motor Company App-2 Fan and Pump
1.0 P parameters (P1 thru P5) and Engineering Unit Selection Summary.
Table 1.0.1summarizes the P parameters and will be explained more in detail in the next section.
Table 1.0.2 summarizes the Engineering Units that can be used and displayed.
Table 1.0.1 MA7200 PLUS Inverter Series P1 to P5 Parameters
Parameter
No.
LCD Display
Setting Range
Factory Setting
Change During
Operation
Modbus
Address
P1-01
(
Note 1
)
P1-01
Engineering Unit
00 - 25
00
(Set by Cn-28)
NO 0x0600
P1-02
(
Note 2
)
P1-02
Feedback
Maximum
10 - 9999
(Engineering Units
set by P1-01)
0
NO 0x0601
P1-03
P1-03
Local/Remote Key
0: Enabled
1: Disabled (Jog)
0 NO
0x0602
P1-04
P1-04
PID Sleep Function
0: PID Sleep Invalid
1: PID Sleep Valid
0
NO
0x0603
P1-05
P1-05
PID Wakeup Direction
0: Feedback above
1: Feedback below
1 NO
0x0604
P1-06
P1-06
Ext. PID Function
0: Ext. PID Invalid
1: Ext. PID, AO1
output
2:Ext. PID, AO2
output
0 NO
0x0605
P1-07
P1-07
Ext. PID Set Source
0: Set Point
Parameter
1: Terminal VIN
2: Terminal AIN
3: Terminal AUX
4: Set Point RS-485
0 NO
0x0606
P1-08
P1-08
Ext. PID Fbk. Source
1: Feedback Term.
VIN
2: Feedback Term.
AIN
3: Feedback Term.
AUX
3 NO
0x0607
P1-09
P1-09
Ext. PID I Limit
001 - 100%
100%
NO
0x0608
P1-10 Ext.
PID
Filter 0.0
- 2.5s
0.0s
NO
0x0609
P2-01
P2-01
Sleep Start Level
000.00 - 100.00%
000.00%
YES
0x0700
P2-02
P2-02
Sleep Start Delay
000.1 - 600.0 s
0001.0 s
YES
0x0701
P2-03
P2-03
Sleep Wakeup Level
000.00 - 099.99%
000.00%
YES
0x0702
P2-04
P2-04
Sleep Wakeup Delay
000.1 - 600.0 s
001.0 s
YES
0x0703
Cont.