MA7200 PLUS Operating Manual
TECO – Westinghouse Motor Company App-2 Fan and Pump
Table 1.0.3 - Engineering Units Selection by Parameter P1-01
Setting
Engineering
Unit
Description
Setting
Engineering
Unit
Description
0
Set by Cn - 28
13
MPM
meter / minute
1 % %
14 CMM
meter
3
/
minute
2 PSI PSI
15 W
W
3
GPH
gallon / hour
16 kW
kW
4 GPM
gallon /
minute
17 °C
°C
5 inW
Inch
water
18 m meter
6
FPM
feet / minute
19 A
A
7 CFM
feet
3
/ minute
20 RPM RPM
8 in inch
21 SPM
stroke/minute
9 ft feet
22
/s
unit / s
10 HP HP
23
/m
unit / m
11 °F
°F
24
/h
unit / h
12 m/s
meter /
second
25 - none
1.1 P Parameter Specifications
The P parameters, together with interacting parameters from other groups, are used to set and control the following
eleven categories.
1. Scaled Feedback and Engineering units
2. Programmable Local / Remote Switch
3. PID Sleep Functions
4. External PID Functions (Input / Output Terminal)
5. External PID Functions (Gain Setting and Monitoring)
6. Load Loss Detection Function
7. Over Feedback Function for PID Feedback Signal
8. Low Feedback Function for PID Feedback Signal
9. Low Suction Detection Function
10. Flow Meter Display
11. Power Meter, KWh Meter, and Energy Cost Usage.
Although only the P parameters are explained in detail in this note, the user can refer to the appropriate sections of
this manual for further detailed information on the other parameters covered.
Table 1.1.1 Scaled Feedback and Engineering Units
Parameter
No.
LCD Display
Setting Range
Factory Setting
Change During
Operation
Modbus
Address
P1-01
(
Note 1
)
P1-01
Engineering Unit
00 - 25
00
(Set by Cn-28)
NO 0x0600
P1-02
(
Note 2
)
P1-02
Feedback
Maximum
10 - 9999
(Engineering Units
set by P1-01)
0
NO 0x0601
Un-34
Un-34
PID Feedback
Display
---- ----
---- 0x0035
Cont.