Issue/Rev. 0.1 (11/18) ║ MNKS025 • Page 93
5. Verify software seal.
• Select Information
• Verify that the Parameter Seal shows a closed lock
• Select the back button in the upper left hand corner of the display
• Select Maintenance
• Select reset passwords
• Press green accept button
• Verify that an error message is displayed, “Failed to reset passwords
because no flash drive found.” Touch the display anywhere to acknowledge
the
message.
• Select the back button in the upper left hand corner of the display
6. Finding the meter serial number
• Select Configuration
• Select Security Level 4
• Enter 4-digit pin [default is 4444]
• Press Login
• Press
Connections
• Notice that all options are greyed out and that a lock appears in front
of all of the selections.
• The Device Serial Number is shown under the selection and can be
read from this screen. Write down the number for later reference.
• Press the return key (upper left hand corner)
MPU Series C I/O/M Manual
Integrated Touch Screen Display