Page 82 • MNKS025 ║ Issue/Rev. 0.1 (11/18)
7.2.1.2. Connection to Ultrasonic Meter Control Board
The display connects to the ultrasonic meter control board (UMCB) through an ANSI/
IEEE 802.3 Ethernet connection by way of an RJ45 jack.
HMI Display Unit
Ultrasonic Meter Control Board
ETH1
ETH1 or ETH3
7.2.1.3. Display Start-Up
The integrated display will require unique IP addresses that is separate from the main
ultrasonic meter control board (UMCB). The display links to the ultrasonic meter control
board by way of its configured IP address. The factory default network setting for the dis-
play is DHCP where the network automatically assigns this IP address. If the Ultra series
meter is not connected to an Ethernet network or if the network does not support DHCP
then a fixed address may need to be assigned.
Upon power up the unit will proceed through the following boot sequence:
1. TechnipFMC logo screen with boot progress bar
2. For a short period, a configuration icon is shown (gears graphic); if this button is
pressed, the connection sequence in the next item is skipped and the display
connects immediately to the Display main menu.
3. If the display is configured, it will attempt to connect with the host device:
a.
If the Primary URL is configured, the display will attempt to connect to this
host. If the Primary URL fails it will try to connect to the device with the
specified "Device Serial Number".
b. If a host serial number is configured, the display will search the network for
a TechnipFMC device with the specified serial number, obtain an IP address,
and attempt to connect with that host. If it fails with the device serial number it
will attempt to connect to the secondary URL.
c. If a fallback URL is configured the Display will attempt to connect to that host.
4. If step 2 is unsuccessful in connecting to any configured device or if the Remote
Display has not been configured, the Remote Display main menu will be shown. From
the Main Menu the connection settings can be configured and the connection
sequence repeated.
7.3.
Integrated Display Operation
7.3.1.
Display Main Menu
The display's main menu will be displayed if the display does not connect to the UMCB
after powering up sequence. The display's main menu can also be accessed by inter-
rupting the startup process by tapping the screen while the boot icon is displayed. The
following options are provided:
• Configuration – settings for a connection to a device
• Maintenance – adjustment of display setting
• Information – Key identification and settings data
• Reconnect – Initiate a reconnection to the configured device
MPU Series C I/O/M Manual
Integrated Touch Screen Display
Summary of Contents for Smith Meter MPU 1600c
Page 10: ...Page 10 MNKS025 Issue Rev 0 1 11 18 Page intentionally left blank ...
Page 34: ...Page 34 MNKS025 Issue Rev 0 1 11 18 Page intentionally left blank ...
Page 38: ...Page 38 MNKS025 Issue Rev 0 1 11 18 Page intentionally left blank ...
Page 98: ...Page 98 MNKS025 Issue Rev 0 1 11 18 Page intentionally left blank ...
Page 106: ...Page 106 MNKS025 Issue Rev 0 1 11 18 Page intentionally left blank ...
Page 112: ...Page 112 MNKS025 Issue Rev 0 1 11 18 Page intentionally left blank ...
Page 119: ...Issue Rev 0 1 11 18 MNKS025 Page 119 Page intentionally left blank ...