WCL488 Series Water Cooled Electronic Loads
Operation & Programming Manual
TDI-Dynaload Division
Page 6
402828, Rev. B1
Item
Number
Description
5
Voltmeter/Voltage Full Scale Range Selection*
6
Voltmeter (4 digit)
7
Ammeter/Current Full Scale Range Selection*
8
Ammeter (4 digit. Includes two range indicators. AMPS displays actual current.
For K AMPS, multiply the display by 1000 for the actual current.)
9
Wattmeter (4 digit. Includes two range indicators. WATTS displays actual power.
For K WATTS, multiply the display by 1000 for the actual power.)
10
Backlit Alphanumeric Display (This display indicates data input from the front
panel controls [range, mode, and setpoint as entered by the user]. This will also
display other data as selected through the menu selector.)
11
Manual Adjust Knob
12
Manual Adjust Enable
13
Keypad (for numerical entry)
14
Menu Select
15
MEM Preset (up to 10 configurations)
16
Mode Select
CI: Constant Current Mode Select
CV: Constant Voltage Mode Select
CP: Constant Power Mode Select
CR LOW: Constant Resistance (Low Ohm) Mode Select
CR HIGH: Constant Resistance (High Ohm) Mode Select
EXT PROG: Remote Programming Mode Select
SLAVE: Slave Detection
SHORT: Inactive on this product
17
Fault And Warning Status Indicators
SYS: System Fault Indicator
UV: Undervoltage Fault Indicator
OV: Overvoltage Fault Indicator
TEMP: Over Temperature Fault Indicator
I LIM: Current Limit Warning Indicator
P LIM: Power Limit Warning Indicator
SAT: Saturation Warning Indicator
MOD: Module Fault Warning Indicator
* The WCL488 Series offers the selectable full-scale ranges for current and voltage. When a
full scale is selected it changes the full scale of the meter, the current sample, the front panel
adjustments, IEEE controlled adjustments and the analog programming input. This provides an
increase in accuracy and resolution. There are three standard full-scale current ranges and three
standard full-scale voltage ranges.