TCS 3000 Installation
Installation Procedure — Float Electronic Air Eliminator
Installation Procedure:
1.
Locate the air eliminator float wiring on the metering system.
2.
Install the cable gland into the back of the TCS 3000 register
and tighten into the housing.
3.
Run the air eliminator float wiring through the cable gland.
Wire the air eliminator float into the Air Eliminator (AIR
ELIMINAT.) terminal on the board. Leave a small amount of
slack on the wiring.
4.
Compress the cable gland on the TCS3000 register until it is
snug on the air eliminator float wiring.
5.
Locate the air eliminator solenoid wiring on the metering
system.
6.
Install the cable gland into the back of the TCS 3000 register
and tighten into the housing.
7.
Run the air eliminator solenoid wiring through the cable
gland. Wire the air eliminator solenoid into the Auxiliary Re-
lay 2 (AUX 2) on the terminal board. Leave a small amount of
slack on the wiring.
8.
Compress the cable gland on the TCS 3000 register until it is
snug on the air eliminator solenoid wiring.
NOTE: Do not run multiple cables through a single cable
Air Eliminator Solenoid
Air Eliminator Float Wiring
RED
BLACK
1/4” NPT Exhaust Vent