Section 7.0 HMI Introduction
HGA IOM
74
6) Running Converter
Press “Setup” to navigate to the setup screen
Select the “Tech Setup” button and enter the password:
08252014
•
Select the “Next” button from the splash screen
•
Select the “Operation Modes” button
•
On the “Operation Mode Setup” screen ensure “PF
Correction Enable” and “Harmonic Correction Enable”
buttons are OFF (Blue). If buttons are green, press to
toggle off TODO and VAR output off.
•
Select the “VAR Output” button and ensure the “Local
VAR Output Enable” and “Network VAR Output Enable”
are OFF (Blue). Select the “Back” buttons to go back to
“Tech Setup” screen
•
Select the “Home” button from navigation bar
•
Select the “Run” button to start unit operation
7) Remove CT shorting bars
•
Press “Stop” to turn off unit
•
Disconnect power from cabinet
•
Turn off the built-in door breaker AND
•
Turn off the upstream feeder breaker
•
Open the cabinet door and remove shorting bars from
CTs connected to TB-1
Warning
Lethal Voltages may be present.
Wait 5 minutes for DC bus Voltage to
drop to safe levels.
Warning
Check for Voltage in cabinet with a
DMM before working inside cabinet.